119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08

TANDBERG

Telepresence T3

ACOUSTICS REQUIREMENTS

It is essential to have a good acoustic environment for the system to provide the 
true telepresence experience. This means that there should be sufficient sound 
insulation to minimize noise from adjacent rooms and to ensure that confidential 
information is kept within the meeting room. A good choice of acoustic materials 
for the surfaces and low background noise will ensure comfort in long meetings 
in addition to high speech intelligibility. You may want to contact acoustic 
specialists when looking into this matter. 

REQUIREMENTS IN GENERAl

All walls around the room should have a sound insulation of R’w 

 48 dB 

(corresponding to STC 50). 

The door should have a sound insulation of Rw 

 38 dB. 

Background noise level should be less or equal to 30 dB(A). This includes both 
noise from technical installations (air-conditioning in particular) and outdoor traffic 
noise etc. 

REQUIREMENTS SPECIfIC fOR IMMERSIVE ROOMS

Absorptive ceiling should have an absorption factor α

 0.9 in the octave bands 

125–4000 [Hz]. This will normally require a mineral wool ceiling of good quality. 

REQUIREMENTS SPECIfIC fOR NON-IMMERSIVE ROOMS

Reverberation time (RT) should be within 0.3–0.6 [s] in the octave bands  
125–4000 [Hz].

The acoustic absorption should to some extent be distributed on the walls in 
addition to the ceiling to avoid flutter-echo effects from parallel walls.

The ceiling is recommended to have an absorption factor  

 0.9 in the octave 

bands 125–4000 [Hz]. This will normally require a mineral wool ceiling of good 
quality. 

The walls should at least have sound absorbing fields at the side, front and back 
walls corresponding to the TANDBERG Immersive Room Package. Both the 
placement and area should be approximately the same. If perforated or slotted 
panels are used, the opening area of the panel must be at least 20

 

%. 

Sound absorption on walls could also be made with mineral wool wall panels, 
curtains or other absorptive materials. 

Содержание Telepresence T3 119076.02

Страница 1: ...way Tel 47 67 125 125 Fax 47 67 125 234 Video 47 67 126 126 E mail tandberg tandberg com 1212 Avenue of the Americas 24th Floor New York NY U S A 10036 Tel 1 212 692 6500 Fax 1 212 692 6501 Video 1 212 692 6535 E mail tandberg tandberg com www tandberg com contents Room requirements 1 System dimensions 2 Room depth requirements optimal and maximal depth 3 Minimum room depth requirements 4 Minimum ...

Страница 2: ...2 TANDBERG Telepresence T3 119076 02 TELEPRESENCE T3 ROOM REQUIREMENTS 12 08 SYSTEM dimensionS 1658 65 1 4 T3 system dimensions 2800 110 1 4 1650 65 1650 65 1500 59 2500 65 3 8 120 4 3 4 724 28 1 2 5 8 4800 189 ...

Страница 3: ...15 40 1000 39 3 8 1300 51 1 8 Centerline Baseline Optimal room depth 2800 110 1 4 140 5 1 2 500 19 3 4 The 1300 mm is vital and should not be exceeded Otherwise the floor the skirting boards and the wooden panels start to become visible on the screen image Note The door is not a part of the TANDBERG Immersive Room Package The door should be mounted so that it opens outwards ...

Страница 4: ...0 162 1 4 4400 173 1 4 1015 40 1000 39 3 8 1300 51 1 8 Centerline Baseline Min room depth 2800 110 1 4 140 5 1 2 20 3 4 Observe that if the room gets smaller the space between the table and backwall will be tight Note The door is not a part of the TANDBERG Immersive Room Package The door should be mounted so that it opens outwards ...

Страница 5: ...dth 4800 189 6645 261 5 8 922 5 36 3 8 922 5 36 3 8 85 3 8 3 6815 268 1 4 85 3 8 3 Observe that the room should not have a smaller width than shown since that will prevent a proper installation of the wooden corner panels Note The door is not a part of the TANDBERG Immersive Room Package The door should be mounted so that it opens outwards ...

Страница 6: ...Telepresence T3 119076 02 TELEPRESENCE T3 ROOM REQUIREMENTS 12 08 Optimum and maximum ROOM HEIGHT 2360 92 7 8 190 7 1 2 2550 100 3 8 optimal room height Note that the room is shown with the Telepresence T3 system installed ...

Страница 7: ...Telepresence T3 119076 02 TELEPRESENCE T3 ROOM REQUIREMENTS 12 08 minimum ROOM HEIGHT REQUIREMENTS 2360 92 7 8 40 1 5 8 2400 94 1 2 minimum room height Note that the room is shown with the Telepresence T3 system installed ...

Страница 8: ...BERG Telepresence T3 119076 02 TELEPRESENCE T3 ROOM REQUIREMENTS 12 08 Maximum ROOM HEIGHT 2360 92 7 8 290 11 3 8 2650 104 3 8 maximum room height Note that the room is shown with the Telepresence T3 system installed ...

Страница 9: ... with the ceiling lights positions nor the document camera position A detailed drawing of the ceiling mounting of the lights can be found overleaf while the drawing 119082 on page 14 shows the position of the document camera Note Dimensions are between floor and underside of light modules Note The HVAC equipment must not be mounted in a way so that it prevents correct mounting of the ceiling light...

Страница 10: ...rline Baseline 320 125 8 2247 881 2 2100 825 8 150 57 8 2025 793 4 675 265 8 2280 89 3 4 Make sure that HVAC mounting neither conflicts with the ceiling lights positions nor the document camera position The drawing 119082 on page 14 shows the position of the document camera HVAC REQUIREMENTS ...

Страница 11: ...ons air conditioning in particular and outdoor traffic noise etc Requirements specific for immersive rooms Absorptive ceiling should have an absorption factor α 0 9 in the octave bands 125 4000 Hz This will normally require a mineral wool ceiling of good quality Requirements specific for non immersive rooms Reverberation time RT should be within 0 3 0 6 s in the octave bands 125 4000 Hz The acoust...

Страница 12: ...Back wall C 2 Touch collaboration display splitter 20 Back wall C 2 Touch collaboration display 750 Back wall C 2 Document camera 300 Ceiling D 2 T3 Ceiling mounted lights 750 Ceiling D 3 T3 LED Module 1000 Back Front wall D 4 Total power 9335 Note The table lists minimum fuse requirements All electrical work must be done by electricians with local knowledge Note Outside the room adjacent to the e...

Страница 13: ...are also available in electronic formats as pdf dwg and dxf To obtain copies of these drawings send an e mail to tandberg tandberg com The following drawings are available 119082 T3 Ceiling 119083 T3 Electrical System 119083 US T3 Electrical System US 119084 T3 Furniture Plan 119086 T3 Short Structure 119087 T3 Long Structure 119088 T3 Structural Elements 119089 T3 Lighting ...

Страница 14: ...n should be avoided Installation area for ceiling mounted document camera see separate installation guide No air condition in this area T3 Ceiling 119082 Doc Title Sign Date Revision Related Tandberg Product TANDBERG T3 1 25 A3 Drw No Unit mm Scale Sheet Size TANDBERG 04 11 08 01 www tandberg com Note The door is not a part of the TANDBERG Immersive Room Package The door should be mounted so that ...

Страница 15: ...ndberg com Doc Cam location in suspended ceiling 110V 30A 220V 16A Ceiling hardwire outlet Light Fuse Power outlets A B C D Doc Cam Ceiling lights and LED module Fuse D 17 11 08 02 All Hardwire outlets Fuse D 4 01 12 08 03 A A A B C A A B C Hardwire outlet for light mounted sideways on wood lattice Hardwire outlet for light mounted sideways on wood lattice LED 5 LED 4 LED 3 LED 2 LED 1 3 x junctio...

Страница 16: ...loor Cable Routing Transport cables from T3 Unit mm Scale Sheet Size Drw No TANDBERG T3 Electrical System US 04 11 08 01 119083 US www tandberg com Doc Cam location in suspended ceiling 110V 30A 220V 16A Ceiling hardwire outlet Light Fuse Power outlets A B C D Doc Cam Ceiling lights and LED module Fuse D 17 11 08 02 All Hardwire outlets Fuse D 8 01 12 08 03 A A A A A A B C A A A A A A B C Hardwire...

Страница 17: ...50 138 1 2 140 5 1 2 140 5 1 2 4098 50 161 1 2 2250 88 1 2 740 29 10 1 2 20 1 2400 94 1 2 4600 181 Centerline Optional Second row rear edge of foot plate 04 11 08 T3 Funiture Plan 01 119084 Doc Title Sign Date Revision Related Tandberg Product TANDBERG T3 Drw No Unit mm Scale Sheet Size TANDBERG www tandberg com 1 25 A3 ...

Страница 18: ...s Gap between the vertical lattices 300 approx 600mm 977 38 1 2 625 24 1 2 2311 91 945 37 300 12 300 12 1000 39 1 2 1026 5 40 1 2 Frame around area for insulation boards Distance of the first lattice from corner lattice 300 11 8 01 04 11 08 T3 Short Structure 119086 Doc Title Sign Date Revision Related Tandberg Product TANDBERG T3 Drw No Unit mm Scale Sheet Size TANDBERG www tandberg com 1 25 A3 ...

Страница 19: ...090 82 1 2 3056 70 120 1 2 3596 70 141 1 2 1485 58 1 2 Centerline Area for mounting changing Led Frame around area for insulation boards 04 11 08 01 T3 Long Structure 119087 Doc Title Sign Date Revision Related Tandberg Product TANDBERG T3 Drw No Unit mm Scale Sheet Size TANDBERG www tandberg com 1 25 A3 ...

Страница 20: ...557 61 1 2 3757 148 80 3 1193 47 Center line Base openings Base opening Base opening Structural element Structual element Floor power outlet recommended hole T3 Structural Elements 04 11 08 01 119088 Doc Title Sign Date Revision Related Tandberg Product TANDBERG T3 Drw No Unit mm Scale Sheet Size TANDBERG www tandberg com 1 25 A3 ...

Страница 21: ...ng Picture center 20 3 4 69 2 3 4 DETAIL D SCALE 1 5 Removable baseboard for access to outlets Mounted with magnets Power LAN outlets Hardwire outlet for LED lights LED mounted on bracket T3 Lighting 04 11 08 01 119089 17 11 08 02 01 12 08 03 Doc Title Sign Date Revision Related Tandberg Product TANDBERG T3 Drw No Unit mm Scale Sheet Size TANDBERG www tandberg com 1 25 A3 ...

Страница 22: ...Cabling 119168 04 11 08 01 www tandberg com Wiring of RS 232 cable from Doc Cam to T3 cable tray above suspended ceiling Wiring of VGA cable from Doc Cam to T3 cable tray above suspended ceiling 17 11 08 02 01 12 08 03 Hardwire outlet for light mounted sideways on wood lattice LED 5 LED 4 LED 3 LED 2 LED 1 3 x junction box Leader Cable LED organisation Europe Junction box and extra cables supplied...

Отзывы: