4.1.5
Cabinet and Rack Ventilation
The cooling airflow for the subrack enters through the front panel and exits
at the rear. For optimum thermal performance, the heated air that passes
through a base station must never be allowed to re-enter the air intakes on
the front panel. Any space at the front of the cabinet not occupied by
equipment should be covered by a blanking panel. Refer to
Equipment installation should observe the following guidelines:
■
The recommended maximum number of subracks in a 38U cabinet is
five as shown in
.
■
Any space at the front of the cabinet not occupied by equipment should
be covered by a blanking panel. Refer to
■
Subrack placement in the cabinet should include a 2U gap at the top of
the cabinet.
■
To allow enough cooling airflow through a cabinet-mounted base
station, the cabinet should allow for 50 cu.ft/min for each subrack
(0.024 cu.m/s).
■
To ensure adequate ventilation, the cabinet should have a vent at the top
with an area of approximately 23in
2
(150cm
2
) per subrack, or a similar
area of ventilation per subrack at the rear of the cabinet behind each
subrack.
■
The maximum ambient temperature at the base station front panels must
not 140°F (+60°C).