1
TK10200 (51.2V 200Ah)
Lithium Iron Phosphate Battery
User Manual
Страница 1: ...1 TK10200 51 2V 200Ah Lithium Iron Phosphate Battery User Manual...
Страница 2: ...imensions 5 4 2 Battery Parameters 5 4 3 Interface Definitions 6 5 LiFePO4 Battery Safety Operating Guidelines 9 5 1 Application Schematic 9 5 2 Tools 9 5 3 Security equipment 9 6 Installation 10 6 1...
Страница 3: ...e battery charge percentage shall not be less than 70 5 If the battery is fully discharged it should be charged within 12 hours 6 Before maintenance batteries and equipment must be cut off firstly 7 D...
Страница 4: ...it for connecting this battery with any faulty or incompatible devices 1 2 4 When fire occurs only dry powder fire extinguishers can be used liquid fire extinguishers are prohibited 1 2 5 Do not disas...
Страница 5: ...ation can balance the battery module each single string core Expansion flexible configuration multiple battery modules can be parallel expansion capacity applicable to different standby time requireme...
Страница 6: ...m 482 500 280 Weight About 84KG Working voltage 43 2 58 4V Charging voltage 56 8 58 4V Charging current limiting 10A The default charging current is greater than 55A and the current limiting is on Sta...
Страница 7: ...LED indicator lights up for 0 5 seconds from the lowest power lamp When the BMS is activated press reset button for 6 seconds and release the protection board is reset and the LED lights are lit for...
Страница 8: ...8 4 3 2 RS485 2 With a dual RS485 interface the default baud rate is bps 9600 can be expanded in parallel battery pack communication interconnection 4 3 3 RS232 Default baud rate bps 9600...
Страница 9: ...ial switch position 1 2 3 4 0 OFF OFF OFF OFF 1 ON OFF OFF OFF 2 OFF ON OFF OFF 3 ON ON OFF OFF 4 OFF OFF ON OFF 5 ON OFF ON OFF 6 OFF ON ON OFF 7 ON ON ON OFF 8 OFF OFF OFF ON 9 ON OFF OFF ON 10 OFF...
Страница 10: ...rrent protection Elimin ation Elimin ation Elimina tion Elimina tion Elimin ation Elimi natio n Stop discharge Temperature overcurrent short circuit reverse connection failure protection Elimin ation...
Страница 11: ...idelines 5 1 Application Schematic 5 2 Tools The following tools are needed to install batteries Use insulated tools to prevent accidental electric shock or short circuit If there is no insulation too...
Страница 12: ...etween 0 c and 50 C the temperature and humidity remain constant 6 1 5 This area has little dust and dirt Attention If the ambient temperature is out of working range the battery pack will stops to wo...
Страница 13: ...own below Note When the battery is placed or pulled out of the rack beware of the battery slipping out Note when connecting the equipment the battery output positive and negative electrodes should be...
Страница 14: ...alarm Please check whether the battery connection is correct or over current then press the RST reset key to see if the failure is eliminated after the battery restarts If it can not be eliminated ple...
Страница 15: ...urrent state until the charger can be activated at the charging input end 8 3 Temperature Protection ALM alarm indicator lights flicker RUN operation indicator lights out Cause analysis Ambient temper...