7.4.4
Description of pump operation in P1+P2 interlock control
The operation proceeds with reference to the P2 supply pressure, P1 maximum pressure setting value
and current value.
P1 set pressure = P1 maximum pressure
P2 set pressure = P2 supply pressure
➔
(P2 C.V > P2 S.V) : Stops the motor.
➔
(P2 C.V < P2 S.V) and (P1 C.V > P1 S.V) : Stops the motor.
➔
(P2 C.V < P2 S.V) and (P1 C.V < P1 S.V) : Motor operation.
➔
(P2 C.V > P1 C.V) : Alarm triggered
List
Description
This is a setting that sets off an alarm before the material is
exhausted.
➔
When set to 5%, an ALARM occurs when the
remaining material reaches 5%
Sets the pump control method.
➔
PID control progress when RPM gain value is 0.
➔
When the RPM gain value is not 0, the RPM gain
value is the RPM value operated per second.
Ex) If the RPM gain value is 1, the motor operation increases
by 1 RPM per second.
Control operation type can be set through external
communication.
➔
LOCAL : PRO-CPD20 front panel button control
➔
REMOTE : PRO-CPD20 operation control by external
signal