tae TA-05KB-SMD Скачать руководство пользователя страница 1

TA-05KB-SMD

& TA-1K-SMD

Instruction & Operating manual

State 02.02.2017 V-2 TAE_BA TA-05KB_TA-1K_EN.PMD The German text applies in cases of doubt

Pikatron GmbH • division TAE Antriebstechnik • Raiffeisenstrasse 10 • D-61250 Usingen

Warnung:

As with any form of electrical equipment, there is always a risk involved in the handling of electrical machinery. The 

greatest care must always be exercised during installation and maintenance, and it is recommended this be carried 

out by authorized personnel. 

Содержание TA-05KB-SMD

Страница 1: ...ikatron GmbH division TAE Antriebstechnik Raiffeisenstrasse 10 D 61250 Usingen Warnung As with any form of electrical equipment there is always a risk involved in the handling of electrical machinery The greatest care must always be exercised during installation and maintenance and it is recommended this be carried out by authorized personnel ...

Страница 2: ...max 10A Field voltage 210V Field current max 0 5 Ampere max 0 6 Ampere Ambient temperature 0 40 C Speed accuracy 3 with armature feedback 1 with tachometer feedback Semi controlled single phase bridge inner loop current regulator acceleration integrator Table of content 1 Technical data 2 2 Connection of the drive control refer to connectiondiagramm 3 3 Drive control adjustment 3 4 Indicator lamps...

Страница 3: ...round terminal 14 negative approx 150 V at rated motor speed Matching of tachometer with R36 9 10 11 Speed potentiometer connect center to terminal 10 start to terminal 11 and end to ter minal 9 This potentiometer enables an infinite variable adjustment of the motor from min to max speed 3 Drive control adjustment Min RPM P1 Adjustment of minimum speed during operation Acceleration rate P2 Adjustm...

Страница 4: ...r speed with P3 max speed for the requested maximum value Now turn the speed potentiometer fully counter clockwise the output voltage must drop back to 0 V and the potentiometer P1 min speed can now be adjusted for the requested minimum speed 9 Adjust the I x R compensation with potentiometer P4 Check for approximate equal speed with and without motor load in the lower speed range When the potenti...

Страница 5: ...ED 2 line does not light up c defective fuse Si 10A FF TA 1K 16A FF TA 1K d relay K1 is defective a motor load is to high b defective speed potentiometer c current limit is set to low Relay K1 is not energized when drive is re leased yellow diode LED 1 does not light up Drive runs unstable a I x R compensation is set to high when armatu re feedback controlled b defective tachometer or tachometer l...

Страница 6: ...r defective tachometer b check armature feedback c potentiometer P3 max speed is defective Drive runs after release at maximum speed wit hout keeping reference value preset speed a intermittent potentiometer P1 min speed b intermittent speed potentiometer or intermittent wiring from terminal 11 to potentiometer Motor starts immediately when connected to AC line without drive being released a groun...