1-36
Coral IPx 500 Installation Manual
General System De
script
ion and Installation
1
Mounting the Cage onto the Rack:
1.
Verify the cage mounting position on the rack. In addition to customer
requirements, requirements for heat dissipation need to be taken into account. See
page 1-11, Space and Positioning Requirements
2.
Assemble the mounting bracket according to rack size. See
Cage for 19" Rack-Mounted Configuration
OR
page 1-36, Preparing the Cage for 23"
3.
For 19" rack configurations, remove the front door and set it aside to obtain access
to the bracket fasteners. See
4.
Lift the cage to the mounting position on the rack.
5.
Insert the hanging pins (
) into the two
square holes on the rack. This ensures that the cage remains in position while it is
fastened to the rack.
Do not
let go of the cage after you have inserted the hanging
pins. The hanging pins are not designed to support the weight of the cage and are
to be used only for assistance.
Mechanical Hazard! Insecure mechanical loads could result in injury or death. If the
cage is mounted onto a rack, it is the customer’s responsibility to ensure that the cage is
tightly secured to the frame and that the cage cannot be inadvertently released from the
rack.
Ergonomic Hazard. The cage weight is provided in
. Serious
back injury could result due to improper handling. Use proper lifting techniques to mount
the cage onto the rack.
Ergonomic Hazard. The hanging pins are not designed to support the weight of the
cage.
Do not
rest the weight of the cage on the hanging pins. Continue to support the
cage until it has been securely fastened to the rack.
Содержание Coral IPx 500
Страница 1: ...Quick Installation Guide The flexible way to communicate Coral IPx 500 DRAFT 3...
Страница 10: ......
Страница 60: ...1 50 Coral IPx 500 Installation Manual General System Description and Installation 1...
Страница 70: ...2 10 Coral IPx 500 Installation Manual Main and Expansion Cage Description Coral IPx 500 2...
Страница 85: ......