23
7.9
Settings
MENU
The visible values vary depending on the selected hydraulic variant, as well as option, and depend on the input password, "Key" column.
Menu
Description
Range
Unit
Value
Key
ID
MENU
BAS BASIC
BAS01 Tset, domestic hot water
Nominal temperature value
- Fresh water station
... for the DHW production, the value at TWW should
be reached and held using the speed controller of the
primary pump.
10 ... 90
°C
0
05:051
BAS02 Scalding protection
Max. permissible over-
shoot DHWSet
... of the DHW nominal temperature value (secondary
side). If exceeded, the primary pump is switched off.
0 ... 30
K
25
05:098
BAS03 TWW sensor type
TWW DHW sensor, sensor
type selection
0: NTC 5K
1: PT 1000
2: 0 … 5 V
0 ... 2
-
25
36:016
BAS04 TKW sensor type
TKW cold-water sensor,
sensor type selection
0: NTC 5K
1: PT 1000
2: 0 … 5 V
0 ... 2
-
25
36:017
ZIR00 Circulation mode
Circulation pump function 0 = Off
1 = Temperature-cont time program
3 = Temperature-controlled
4 = Pulse-controlled
5 = Time program
6 = Temperature- + pulse-controlled
7 = Temperature- + pulse-cont time program
8 = Pulse-cont time program
0 ... 8
-
0
05:006
SCH00 Return layering
Option: Return layering
Function for layering the return temperature in the
buffer. With this parameter the function can be activat-
ed and the logic of the diverting valve can be inverted.
-1: relais closes if TPR is warm (for top of buffer)
0: option deactivated
1: relais closes if TPR is cold (for bottom of buffer)
-1 ... 1
0
0
05:110
LEG00 Therm. Disinfection
Thermal disinfection func-
tion
The DHW is first heated to the set legionella protection
temperature according to the setting and maintained
for the minimum holding time.
0: No function
15: With pump WWC and TBZ
16: With pump WWC and TKW
17: With pump WWC and TWW
18: With pump WWC and TBZ; TKW; TWW
Note:
Adjusters only visible if BAS03 > 0.
0 ... 18
-
0
05:014
NAC00 Recharging, primary
Option: Rech. / therm.
... for (re-)charging the primary energy storage.
on/off
off
0
08:110
BAS05 Warming function
Option: Ready / warming
function
...keeps the heat exchanger at a ready temperature to
ensure quick DHW production.
on/off
off
25
05:113
BAS09 Time
Time
00:00
-
0
02:072
BAS10 Date§
Date
yyyy
dd:mm
-
0
02:070
BAS15 Tmin heatsource
Primary/tank minimum
temperature
If the temperature in the tank < this set value, the sta-
tion switches off and generates status message "11"
0 ... 90
°C
25
05:058
PAR Parameter
ZIR Circulation
Adjuster visible if
Circulation mode BAS03
(05:006) is set not equal to 0.
ZIR00 Circulation mode
Function pump circulation
0 ... 8
-
0
05:006
ZIR01 TD Circulation set point
Nominal value reduction
for circulation return
Nominal value reduction for circulation return, results
in the circulation nominal temperature value which is
to be reached at the TBZ sensor. TBZSet = TWWSet -
TWWSetReturn
0 ... 90
°C
0
05:054
ZIR02 Tmax circulation
Max. circulation tempera-
ture
Maximum temperature for limiting the temperature
load in the circulation lines
0 ... 90
°C
25
05:072
ZIR04 TBZ sensor type
TBZ circulation sensor,
sensor type selection
0: NTC 5K
1: PT 1000
0 ... 1
-
25
05:088
ZIR05 Circ. calib. tolerance
Circulation flow tolerance
Circulation flow tolerance.
Max. permissible deviation among flow measure-
ments during calibration.
0 ... 100
%
25
36:011