17
7.3.1
Adapting the standard display
Accept value on standard display:
Select the measured temperature or data value to be accepted as described in sect. 7.3,
page 16. Keep the
key pressed until "YES" appears on the display. The value is
shown on the standard display.
7.3.2
Resetting energy data
Reset energy in kWh:
The energy can be reset manually. The current value is set to zero by pressing the
key for a few seconds. If the
key is pressed, the display in kWh is reset to "0" again.
7.4
Values on information level
INFO
The visible values vary depending on the selected hydraulic variant, as well as the option, and depend on the input password, "Key" column;
see sect. 7.6, page 20.
Menu
Description
Range
Unit
Value
Key
ID
INFO
STA STATUS
STA01 Status
Status of the DHW produc-
tion
0 : Switched off
2 : Thermal disinfection / comfort mode
5 : Fault
6 : Tapping/ DHW withdrawal
7 : Warning
8 : Nominal value reduction
10 : Reheating
11 : Cancel charging
14 : Standby station in cascade
0 ... 11
-
-
0
02:052
STA02 Circ. Calibration
Status of circulation flow
calibration
0: Inactive
Calibration not done yet or last calibration obso-
lete.
1..8: Active, measurements 1..8.
If measurements 1..4 OK, transition into 9; other-
wise, carry out measurements 5..8 and then eval-
uate.
9: Calibration successful.
10: Start.
11: Error - Flow despite pump being switched off.
12: Error - Flow rate fluctuations too great with the
pump switched on.
0
STA03 Thm.disinfection info
Information about thermal
disinfection
... with time specified when this was successfully car-
ried out.
yyyy
dd:mm
-
-
0
02:127
STA04 Speed, pri. pump
Current control variable
Output 1
0 ... 100
%
-
0
22:031
STA05 Output, circ. pump
Current control variable
Output 2
0 ... 100
%
-
0
22:032
STA06 Current control variable A3 Current control variable
Output 3
0 ... 100
%
-
0
22:033
STA07 Current control variable A4 Current control variable
Output 4
0 ... 100
%
-
0
22:034
STA08 Current control variable A5 Current control variable
Output 5
0 ... 100
%
-
0
22:035
STN1 Station casc. status
Status during cascade op-
eration
... of the station in the FW cascade manager:
Digit 1:
Sequence number of the station, range 0..5,
0: Station not available
Digits 2..4: Control signal s of the KM for this station:
0: Off
1..100: Override with s%
101: Not ready, no energy
102: Standby
103: Control
00 ... 1103
-
-
0
02:123
STN2 Station casc. status
Status during cascade op-
eration
00 ... 2103
-
-
0
STN3 Station casc. status
Status during cascade op-
eration
00 ... 3103
-
-
0
STN4 Station casc. status
Status during cascade op-
eration
00 ... 4103
-
-
0
STN5 Station casc. status
Status during cascade op-
eration
00 ... 5103
-
-
0