ANOMALIES: CAUSES AND REMEDIES
DANGER
IT IS FORBIDDEN TO USE THE CIRCULATOR IN THE PRESENCE OF ANY TYPE OF ANOMALY.
DURING MAINTENANCE IT IS FORBIDDEN TO LEAVE THE CIRCULATOR UNATTENDED AND WITHOUT PRECAUTIONS TO PREVENT
ACCESS TO UNAUTHORISED PERSONS.
DANGER
IF THE MAINTENANCE TECHNICIANS CANNOT RESOLVE THE ANOMALY, THE MANUFACTURER MUST BE ASKED TO INTERVENE.
DANGER
ALL MAINTENANCE ON THE CIRCULATOR MUST BE PERFORMED WITH THE CIRCULATOR IN THE
SAFETY STATE
.
Anomaly
LED indication
Causes
Remedies
1) The circulator
is noisy
On
The suction pressure is
insufficient - Cavitation
Increase the system input
pressure within the allowable
range
On
Foreign bodies in the impeller Check if there are foreign bodies
inside the pumping body
2) Loud liquid
circulation
noise
White flashing
light on
Air in the system
Vent the system
On
The flow rate is too high
Reduce the rotation speed
3) The circulator
does not start
Off
No power supply
Check the voltage of the
electrical system.
Check the connection of the circulator
A system fuse is defective
Check the fuses and replace
them, if necessary
The circulator is defective
Replace the circulator
Red flashing light on Overtemperature
Wait for the circulator to cool
and verify it restarts.
Check that the liquid temperature and
ambient temperature are within the
TAB. 24
(Anomalies: Causes and remedies)