background image

Application: 

Taco Zone Sentry Zone Valves can be used in a wide vari-
ety of heating and (non condensing) cooling applications,
primarily designed for use with baseboard, fan coils, radia-
tors, convectors, air handlers, heat pumps and radiant
applications. Refer to the Product Specifications section for
choosing the correct style valve for your application.

General Installation Information / Operation:

The Zone Sentry is the most technologically advanced
zone valve ever made. It’s also simple to install and oper-
ate. The valve body can be installed in any position and
in any orientation. The actuator’s electrical connections
must be mounted over the port that requires flow when
power is applied to the actuator. (See Figure 1.) The back
of the valve makes for a simple, secure and fast wiring
hook-up. A green LED light shows full functionality of the
valve’s operation and thermostat status. Under a no power
situation the manual override button located on the top
of the valve allows the ball to be rotated up to 90°.  

Before mounting the body refer to Figure 2 for any clear-
ance requirements. 

Use of a solder with a melting point below 600°F is rec-
ommended. Do not overheat! Make sure the ball valve is
in the FULL OPEN position to the port that is being sol-
dered. Direct flame tip away from the center of the valve.
Cool valve quickly with a wet rag to prevent overheating.
Solder build-up on the ball valve may prevent proper
opening and closing of the valve. 
Valve body may be submerged for leak testing before the
actuator is attached.

Step by Step Valve Installation:

1. Remove actuator from the valve body. Push in and

hold the release clip at the front of the actuator, pull
the actuator away from the body (approx. 

3

4

"). (See

Figure 3.)

2. Open the valve to the full open position of the first

port to be soldered (port A or B). 

3. Clean and prepare the valve and pipe using the

proper techniques required prior to soldering.

4. Fit the valve into the piping system.
5. Solder the port of the valve that you placed in the

full open position, directing the flame away from
the center of the valve.

6. Turn the opening of the valve to the second port to

be soldered. (the opposite port of the one just com-
pleted.) 

7. Repeat step 5 for the second port.
8. Solder the third port (bottom port). This port is

always in the full open position.

9. Immediately cool the valve with a wet towel.

Instruction Sheet

Zone Sentry 3-way Diverting Valve

102-426

SUPERSEDES: New

EFFECTIVE: April 1, 2011

Plant ID# 001-3997

CAUTION: Actuator must be removed from
the valve body before soldering (see
Figure 3). Ball valve must be in the full open
position to the port that is being soldered.

1

3

8

" CLEARANCE

3

4

" CLEARANCE

W

A

L

L

Figure 2

A

C

B

A

C

B

CALL

CALL

NO CALL

NO CALL

ELECTRICAL

CONNECTION

ELECTRICAL

CONNECTION

Figure 1

L

OCKING

POST

Step 1:
Push in and hold
release clip at the
front of the actuator.

Step 2:
Move actuator away from the
valve body approximately 3⁄4"
to disengage locking posts
and stem.

Figure 3: Operator

Removal

CAUTION:  Installation should only be per-
formed by a qualified professional.

Содержание Zone Sentry

Страница 1: ...g and closing of the valve Valve body may be submerged for leak testing before the actuator is attached Step by Step Valve Installation 1 Remove actuator from the valve body Push in and hold the release clip at the front of the actuator pull the actuator away from the body approx 3 4 See Figure 3 2 Open the valve to the full open position of the first port to be soldered port A or B 3 Clean and pr...

Страница 2: ...mostat is satisfied the green LED will turn OFF and the valve will rotate 90 into its nor mal position or non powered position WARNING Do not use zone valves on indirect water heaters without a tempering device Product Specifications Maximum Operating Pressure 300 PSI 2 100 kPa Maximum Shutoff Pressure 125 PSI 875 kPa Fluid Temperature Range 20 to 240 F 7 to 115 C 135 F 57 C ambient Service Closed...

Страница 3: ...t the thermostat instructions for the resistor installation NOTE 2 The plug in quick connects can be disconnected from the valve actuator for ease of wiring Insert the corresponding wire into the quick connects and tighten by turning the screw CAUTION Do not jumper the power motor 24 VAC connection terminals even temporarily This may cause damage to the thermostat s heat anticipator or to the tran...

Страница 4: ...co reserves the right to provide replacement products and parts which are substantially simi lar in design and functionally equivalent to the defective product or part Taco reserves the right to make changes in details of design construc tion or arrangement of materials of its products without notification TACO OFFERS THIS WARRANTY IN LIEU OF ALL OTHER EXPRESS WARRANTIES ANY WARRANTY IMPLIED BY LA...

Отзывы: