iWorx® VPU2
505-010-2, Effective: April 29, 2014
13
© 2014 Taco Electronic Solutions, Inc.
Ground (GND)
Terminal GND
(T40) must be connected to earth ground. Failure to properly ground this equipment will
result in improper operation. Improper grounding may also increase the risk of electrical shock, and may
increase the possibility of interference with radio and TV reception.
Protocol
The VPU2 is based on the L
ON
W
ORKS
®
networking technology and can be networked to a higher-level control system
for monitoring and control applications. For additional information on the Protocol reference the
LonWorks FTT-10A
Free Topology Transceiver User's Guide
, published by the Echelon Corporation.
SPECIFICATIONS
Electrical
Inputs
• Cabling: twisted shielded pair, 18
AWG
recommended—500
feet max. (152
meters)
• Resolution: 10
bit
Mixed Low Limit, Filter Status, Smoke Detect, Local IAQ Alarm
• Dry Contact
• Normally Open
• 5 Volts DC Max
Fan Proof
• Dry Contact
• Normally Closed
• 5 Volts DC Max
Return Air Humidity, Static Pressure
• 0 - 10 Volts DC
Mixed Air Temperature, Supply Air Temperature, Return Air Temperature
• Precon Type III 10K thermistor
Outputs
Cooling Stages 1, 2, 3, & 4; Heating Stages 1 & 2; Fan Start/Stop; Two-position Economizer
• 24
Volts
AC
• 1A @ 50C, 0.5A @ 60C, limited by the Class 2 supply rating
Modulated Economizer, Modulated Static Pressure Fan
• 0-10
Volts
DC
• 2K Ohm minimum load
• 8 bit resolution
Power
Power Requirements
• 24VAC (20VAC to 28VAC), requires an external Class 2 supply
Power Consumption
• 7.2W with no external loads, maximum limited by the Class 2 supply rating