background image

iWorx® LCI3

502-050A, Effective: April 22, 2013

15 

© 2013 Taco Electronic Solutions, Inc.

Setting Temperatures 

To show the temperatures in any of the zones being controlled by the BZU:

1.Press 

All Settings

2.Next, press the Zone that you want to adjust. For example, to adjust Zone 2, press anywhere on that line, as 

shown here: 

3.In the Settings display that appears next, you can see all the settings for that zone. 

To change the temperature in a zone:

1.Press the temperature setting display box that appears beside 

Zone Occ SP

 (Setpoint). A keypad display 

appears, allowing you to enter a new temperture setting.

2.Press the 

CLR

 button on the keypad display. The display box becomes empty.  

3.Insert the desired temperature for that zone by keying in the correct temperature setting.
4.Press the 

SAVE

 key. 

Repeat these steps for each zone temperature that needs to be adjusted.

When the BZU controller that you are working with has been programmed, you can now program the next controller by 
pressing 

HOME

, followed by 

Controllers

. Then press the next control that you want to adjust from the Controllers 

list.

Setting the Hydronic Zone for Controllers

To associate a DXU4 to a BZU, you start from the BZU control screen. Press 

Members

 to display a list of the DXU 

units on the network. The member status of each is shown in the right-hand column. A member unit is one that oper-
ates with shared settings from the BZU. To change the member status of a DXU controller, just press that controller. It 
will toggle member or non-member with each press. If a DXU has been selected or deselected, you must press 

Save

afterward to comfirm the new setting.

If no Hydronic Zone is selected, the DXU4 uses the zone temperature sensor to which it is connected.

DXU3 / DXU4

What it does:

The DXUx controller is used to stage heating and cooling to satisfy the space demands. The DXU4 can also be config-
ured to share temperature readings with a BZU controller. 

NOTE: 

When the DXU is associated to a BZU, the heating setpoint can only be set in the DXUx controller; 

the setting will be sent to the BZU controller automatically!

Содержание iWorX LCI3

Страница 1: ...C 5 Configuring Intranet Communications 7 Configuring Internet WWW Communications 7 LCI3 Quick Start ISP Ethernet Set up 8 Summary 8 Configuring an Email Proxy 8 Configuring the Email addresses 9 Configuring selected alarms to be emailed 9 Selecting Controllers 9 Adjusting Controllers 10 Adjusting Room Temperature Settings 11 Scheduling Occupancy for the Controllers 11 BZU 14 DXU3 DXU4 15 ZXU1 16 ...

Страница 2: ...oduct specifications and for no other pur poses For example iWorx products are not intended for use to support fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other applications where product failure could lead to injury to person loss of life or catastrophic property damage and should not be used for such purposes Description...

Страница 3: ...SD Card input for future control expansion product upgrades or archiving of the databases on the Local Control Interface for backup restore purposes GETTING STARTED The Local Control Interface screen may be in a sleep mode when accessed To activate the screen simply press on the screen anywhere The Local Control Interface now displays the following Password Entry Using a stylus or fingertip press ...

Страница 4: ...the Main Menu simply repeat the instructions for Password Entry above Entering Time and Date If the Local Control Interface has not been commissioned yet you will need to enter the correct time and day Remem ber that the Local Control Interface uses a military 24 Hour time format For example 5 00 PM should be entered as 17 00 If the Time and Date have been entered go to the next section Selecting ...

Страница 5: ...s This exam ple uses Windows 7 as the operating system Please refer to the PC user manual or IT technician if setting up with a different operating system Procedure 1 Determine the PC s IP address and subnet address See also Figure 1 for Windows appearance Right click on the Network icon on the PC s desktop Choose Properties Choose Change Adaptor Settings Right click on Local Area Connection and c...

Страница 6: ...iWorx LCI3 6 502 050A Effective April 22 2013 2013 Taco Electronic Solutions Inc Figure 1 IP Configuration on Microsoft Windows 7 ...

Страница 7: ...n on to the LCI3 Select Utilities from the Home screen Select Network Setup from the Utilities screen Select Ethernet Settings from the Network Setup screen Set Enable DHCP to NO Enter an IP address for the LCI3 This address should be the same as a PC with the last number being differ ent Example PC 10 0 1 59 make the LCI3 10 0 1 60 The address may also be obtained from the IT department NOTE All ...

Страница 8: ... If the LCI3 has not yet been con figured for remote communications via the Internet please reference Configuring Ethernet Communication on page 5 This section provides LCI3 Quick start ISP setup instructions It explains how to Configure the LCI3 to communicate to an ISP Configure the LCI3 to send alarms via email Configure the LCI3 to selectively send emails NOTE This section assumes that the LCI...

Страница 9: ...e immediate attention Some examples of critical alarms are Fan Failure Mixed Low limit freeze condition Smoke detection and Communication failures to name a few NOTE All alarms are enabled by default Alarms need not be disabled if controllers are not installed that support the alarm Procedure 1 Determine which alarms you would like to have annunciated to the email addresses previously entered Sign...

Страница 10: ...every controller on the system You now see every controller on your network when you press Controllers on the Local Control Interface ADJUSTING CONTROLLERS You can configure any controller on the network from the Local Control Interface Keep in mind that controllers may also be renamed and may actually describe the equipment being controlled For example Second Floor First Floor Kitchen and so on T...

Страница 11: ...t temperatures read the instructions for the controller that you have selected NOTE Temperature adjustments made by end users building occupants should always be made at the thermostat or wall sensor not the Local Control Interface Scheduling Occupancy for the Controllers When any controller is first placed on the network it operates in Unoccupied Mode and to its unoccupied setpoints The Local Con...

Страница 12: ...6 Press Monday and the following appears 7 The above periods are in the format Hour Minute to Hour Minute 8 Select the Starting hour in Period 1 that you want to adjust by pressing the hour area where 0 is shown 9 The keypad appears to allow you to set the Hour value 10 Press CLR to empty the box 11 Key in the desired Hour in military format that is key in 17 for 5 o clock PM 12 Press SAVE 13 Repe...

Страница 13: ... press Save only the individual day gets saved If you press Save All the settings are saved for all days of the week Creating a Group A group is a collection of controllers sharing a common schedule In other words a group allows you to choose a single schedule to be associated with multiple controllers To create a group follow these steps 1 On the Home screen press Groups 2 Press Add New 3 Group_1...

Страница 14: ...edule you would like the controllers in the group to follow for example Schedule_1 9 Press Save BZU What it does The BZU controller is used as a zoning control in conjunction with a BLM Series boiler operating control The BZU can control up to 5 zones of heating The BZU can also provide temperature information for cooling when used in conjunc tion with a DXU controller See DXU control for how this...

Страница 15: ...now program the next controller by pressing HOME followed by Controllers Then press the next control that you want to adjust from the Controllers list Setting the Hydronic Zone for Controllers To associate a DXU4 to a BZU you start from the BZU control screen Press Members to display a list of the DXU units on the network The member status of each is shown in the right hand column A member unit is...

Страница 16: ...se steps for each temperature you wish to adjust ZXU1 What it does The ZXU1 is used to control one injection loop for heating cooling or both auto for different tasks It can be config ured for a reset demand with a configurable outdoor reset curve a zone setpoint demand or a snowmelt demand The ZXU1 can be associated to a BLMC controller to generate a heat demand as described in the technical tips...

Страница 17: ...nded twisted pair When connecting temperature inputs Analog sensors to the controller shielded cable is recommended Recom mended wire includes 14 22 AWG shielded twisted pair for all analog inputs with 18 AWG recommended Shields must be connected to an earth ground near the controller Important Config Settings for BLMC and BZUx If BZUx is used to handle high temperatures slate or concrete floors o...

Страница 18: ...ensor such as the iWorX TRW Sensor Remember that this is the ONLY zone being controlled by the BLMC controller Networked BZUx controllers may also create a demand on the BLMC To ensure communications are properly config ured for networked demands please see the above topics Important Config Settings for BLMC and BZUx and Asso ciating a BZU or ZXU to a BLMC How do I Create a Heating Demand on the B...

Страница 19: ...mber this requires a dry contact from the zone panel or end switch wired into the Reset Demand input of the BLMC A BZUx Boiler Zoning Unit or ZXU1 Zone Mixing Unit networked to a BLMC How do I wire zone valves to the BZUx outputs The BZUx outputs simply switch the 24 VAC common leg So all you need to do is bring one side of the 24VAC to one terminal of the zone valve and return the other leg of th...

Страница 20: ...covered by this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other applica tions where product failure could lead to injury to person loss of life or catastrophic property damage and should not be sold for such pur poses If in doubt as to whether a particular produc...

Отзывы: