background image

iWorx® HPU3

20

 

505-035, Effective: June 30, 2015 

© 2015 Taco Electronic Solutions, Inc.

To disable Commissioning, configure the 

Enabled

 parameter in the Commissioning screen to “No.”

Fan Operation

The 

Fan Type

 is configured for either “Auto” or “On.” This setting determines the fan operation when the 

Occupancy 

Mode

 is “Occupied.” This configuration applies to both the digital and modulated fan outputs.

When the 

Fan Type

 is “Auto,” and the 

Occupancy Mode

 is “Occupied,” the fans are energized when there is a call for 

heating or cooling and de-energized when there is no demand for heating or cooling. (i.e. when the space temperature 
is in the zero energy band - between the heating and cooling setpoints).

When the 

Fan Type

 is "On," and the 

Occupancy Mode

 is “Occupied,” the fans are always energized regardless of heat-

ing or cooling demand; the modulated fan output is a minimum of 33%; when there is a heating or cooling demand, the 
modulated fan may increase in speed to satisfy the demand.

Some thermostats allow the fan operation to be overridden. When a thermostat with a single speed fan override is 
used, the fan override energizes the digital fan and the modulated fan output is 100%. When a thermostat with a three 
speed fan override is used, all fan speed overrides energize the digital fan and the modulated fan output is 33%, 67% 
or 100% corresponding to fan speed 1, 2 and 3.

When the 

Occupancy Mode

 is “Unoccupied,” the fans operate as they would when the 

Fan Type

 is “Auto.” 

Dehumidification with Reheat

The controller may be configured for either “External” 

Dehumidification Mode

 or “Internal” 

Dehumidification Mode

“External” 

Dehumidification Mode

 triggers dehumidification equipment using the DHUM digital output. In addition, 

“Internal” 

Dehumidification Mode

 controls the reversing valve and compressor stages. The fan purges for two minutes 

both before and after dehumidification occurs.

Dehumidification begins when the 

Space Humidity

 rises above the configured dehumidification setpoint, and stops 

when the 

Space Humidity

 falls three percent below the dehumidification setpoint. The Reheat (RH) digital output may 

energize during dehumidification.

Both dehumidification and reheat have valid temperature operating ranges. The valid dehumidification range is defined 
as the configurable 

Shutoff Limit

 below the 

Cooling Setpoint

. Reheat only occurs when dehumidifying and the space 

temperature is below the cooling setpoint. Note that the dehumidification range and reheat range are subject to a hys-
teresis to prevent rapid cycling.

To enable dehumidification, configure the 

Dehumidification Type

 as either “Always” or “Occupied,” configure the 

Set-

point

 to a non-zero value (percent), configure the 

Shutoff Limit

 (°F), and configure the 

Dehumidification Mode

 to either 

“External” or “Internal.” Configuration is not required for 

Reheat

.

To disable dehumidification and reheat, configure the 

Dehumidification Setpoint

 to zero. This action disables all dehu-

midification and reheat regardless of other configured values.

Auxiliary Heat

When the Outdoor Temperature is provided by either an ASM or CSM controller, Auxiliary Heating is enabled. When 
the Outdoor Temperature falls below the configured auxiliary heat setpoint, the auxiliary heat digital output (AUX) is 
energized and the compressor stages are turned off. When the Outdoor Temperature rises above the auxiliary heat set-
point plus the configured temperature offset, the auxiliary heat output is deenergized and normal compressor operation 
continues.

To enable auxiliary heat, insure that there is an ASM or CSM controller on the same network as the HPU3. No other 
action is necessary.

To disable auxiliary heat without removing the ASM or CSM controllers from the network, configure the auxiliary heat 
setpoint to a value well below any possible outdoor air temperature. The auxiliary heat setpoint may be configured as 
low as -459.7°F (absolute zero).

Содержание iWorx HPU3

Страница 1: ...evice 6 Routing Cabling to the Device 7 Grounding the Device 7 Wiring Information 8 Connecting Input Devices 9 Connecting Output Devices 10 Other Connections 11 Specifications 11 Electrical 11 Mechani...

Страница 2: ...iWorx HPU3 2 505 035 Effective June 30 2015 2015 Taco Electronic Solutions Inc THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 3: ...tem for monitoring and control applications Features Two stage compressor heating cooling control Reversing valve control Auxiliary Emergency Heat enable Dehumidification with Reheat both internal and...

Страница 4: ...hvac com APPLICABLE DOCUMENTATION See the table below for additional documentation that may be applicable to this controller Description Audience Purpose iWorx LCI Application Guide Docu ment No 505 0...

Страница 5: ...ital device pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference This equip ment can radiate radio frequency energy and if not i...

Страница 6: ...Volts AC To calculate power source current requirements add the power consumption of all peripheral devices to that of the controller The controller and sensor power supplies can use the same power s...

Страница 7: ...control enclosure and wiring conduit Grounding the Device The ground terminal T40 must be securely connected to earth ground Failure to properly ground this equipment will result in improper operation...

Страница 8: ...ons Inc WIRING INFORMATION WARNING Terminals 6 9 and 12 are connected internally on all HPU3 controllers Disconnect ALL power sources when installing or servicing this equipment to prevent electrical...

Страница 9: ...connect the heat pump thermostat or an RH humidity sensor to the unit attach one wire from the thermostat or sensor to STAT T3 and the other wire to the adjacent common T4 Equipment Status EQS To con...

Страница 10: ...e SAT optional To connect a thermistor Precon III to the analog input attach one wire of the sensor to ST T13 and the other wire to the adjacent common T12 Connecting Output Devices Stage 1 Stage 2 S1...

Страница 11: ...wire from a 24 VAC power supply to PWR T39 and the other output wire from the power supply to the adjacent common terminal T38 T38 must be connected to earth ground Ground GND Terminal GND T40 must b...

Страница 12: ...ters For detailed specifications refer to the FTT 10A Free Topology Transceiver User s Guide published by Echelon Corpo ration www echelon com support documentation manuals transceivers Mechanical Hou...

Страница 13: ...control algorithm to minimize excessive cycling As the temperature decreases below the cooling setpoint the compressor stages are sequenced off When the unoccupied mode is entered the cooling setpoint...

Страница 14: ...l alarm is reported to the LCI When the zone humidity rises above the humidity setpoint dehumidification is enabled by activating the dehumidifica tion output external dehumidification and optionally...

Страница 15: ...point offset also affects the calculated heating and calculated cooling setpoints by an equal amount The set point offset only applies in the occupied mode of operation it has no affect in the unoccup...

Страница 16: ...erature drops below the calculated heating setpoint the reversing valve is cycled to the heating position When the space temperature drops below the calculated heating setpoint minus the heating con t...

Страница 17: ...e temperature is less than the space setpoint If the temperature rises above the space setpoint then the minimum on and off times are ignored When the space temperature rises above the space setpoint...

Страница 18: ...ling setpoint for a predefined time period the last energized stage is turned off Note that the last stage that was turned on will be the first one to be turned off If the space tem perature remains b...

Страница 19: ...1 On T1 T2 T1 T2 Reversing Valve COOL Cooling Sequence Unoccupied Mode Commissioning The controller has a Commissioning screen that allows any of the controller s outputs to be manually configured to...

Страница 20: ...after dehumidification occurs Dehumidification begins when the Space Humidity rises above the configured dehumidification setpoint and stops when the Space Humidity falls three percent below the dehu...

Страница 21: ...o zero percent humidification is not enabled Thermostat Space temperature current humidity setpoint adjustment fan auto on status depending on the thermostat model and occupancy override request are m...

Страница 22: ...ly closed active when open When a pressure alarm input becomes active a high or low pressure alarm message is sent to the LCI and the heat pump outputs are disabled When the pressure alarm clears norm...

Страница 23: ...n the HPU3 with LNS or other LONWORKS tools if they wish The LCI also provides network supervision of the HPU3 The LCI periodically sends a ping message to the HPU3 which elicits a response If the res...

Страница 24: ...go beyond the Supply RH Limit nviSetpoint overrides the setpoint as obtained from the thremostat SLink or BZU LCI or a pre configured backup schedule nviOccCmd overrides the occupancy as obtained fro...

Страница 25: ...iResetRuntime SNVT_lev_disc 0 no reset 1 reset runtimes Resets fan heating and cooling runtimes nviSysTime SNVT_time_stamp Date Time System time nviUnitEnable unsigned byte 0 Off 4 On 1 no effect Unit...

Страница 26: ...ature Space Humidity 0 to 100 Space Humidity Supply Air Temp 22 F to 122 F 30 C to 50 C Supply Air Temperature Supply Air Humidity 22 F to 122 F 30 C to 50 C Supply Air Humidity Inst Power 0 to 3 4E38...

Страница 27: ...Off On Status of Dehumidification output DHUM Humidify Off On Status of Humidification output HUM Reheat Off On Status of reheat output RH Auxiliary Heat Off On State of auxiliary heat output AUX Sett...

Страница 28: ...min Allowable occupancy extension time Alarm Temp Offset 0 to 10 0 F 0 to 5 56 C 5 F 2 8 C Degrees below the heating setpoint or above the cooling setpoint to trigger a low limit or high limit alarm...

Страница 29: ...55 minutes 5 minutes Compressor control cycle timer Setting Range Default Description Setpoint 459 to 621 F 273 to 327 C 20 0 F 6 7 C The outside air temperature OAT that trig gers auxiliary heating T...

Страница 30: ...ormally Open Normally Closed Disabled Enable equipment status High Press Alm Polarity Disabled Normally Open Normally Closed Disabled Enable high pressure status input Low Press Alm Polarity Disabled...

Страница 31: ...e for the alarm limit or reset the accumulated runtimes to zero High Pressure Normal Soft Alarm Hard Alarm Occurs when the High Pressure Alarm input is faulted Alarm is Hard if more than one alarm hap...

Страница 32: ...he controller was previously in an equipment status fault condition the controller must be reset before proper operation can be restored The fan and staged pilot relays will not come on even though th...

Страница 33: ...r A complete description of difficulties encountered Notes Thermistor readings fluctuate rapidly sometimes by several degrees The controller is not properly grounded The controller s ground GND pin T4...

Страница 34: ...overed by this warranty TES products are not intended for use to sup port fire suppression systems life support sys tems critical care applications commercial aviation nuclear facilities or any other...

Отзывы: