Application: 

The Geo-Sentry

®

Zone Valve provides on-off control and is avail-

able in normally open or normally closed configurations. It is espe-

cially suited for use in either open or closed loop geothermal sys-

tems with water source heat pumps.

Ease of Installation / Operation:

The Geo-Sentry

®

is the most technologically advanced zone valve

ever made. It’s also simple to install and operate. The valve can be

installed in any direction, in any orientation except for chilled water

installations (see Figure B). We then went a step further, allowing the

actuator to be mounted to the valve body in either direction (see

Figure A). Snap-in quick connects on the back of the valve make for

a simple, secure and fast wiring hook-up. A green LED light shows

full  functionality  of  the  valve’s  operation  and  thermostat  status.

Under a no power situation the manual override button located on

the top of the valve allows the ball to be rotated up to 90° and is also

marked with a slot to indicate the position of the valve. 

2-Way Valve Installation:

1. On hot water applications, the valve body may be installed in any

orientation. On chilled water installations, do not install with the

actuator beyond 85° from the topmost position (see Figure B).

2. Before mounting the body, refer to Figure C for any clearance

requirements. 

3. Use of a solder with a melting point below 600°F is recommend-

ed. Do not overheat! Make sure the ball valve is in the FULL

OPEN position during soldering. Direct flame tip away from the

center of the valve. Cool valve quickly with a wet cloth.

4. Solder build-up on the ball valve may prevent proper opening

and closing of the valve. Actuate the actuator once or twice and

make sure the valve rotates fully.

5. Valve body can be submerged for leak testing before the actu-

ator is attached.

Actuator Installation / Wiring: 

1. Actuator Removal: Remove the valve actuator prior to soldering

by  pushing  in  and  holding  the  release  clip  at  the  front  of  the

actuator and lifting upward approximately 

3

4

" (see Figure D).

2. To re-assemble the actuator to the valve body: Position actuator

such that the “D” shaped valve stem aligns properly with the “D”

shaped  actuator  drive  cavity.  (Note:  The  “D”  shaped  stem

design allows for correct insertion every time.) Next, slide the

Instruction Sheet

Geo-Sentry

®

Geothermal Zone Valve

102-479

SUPERSEDES: November 1, 2013

EFFECTIVE: October 19, 2017

Plant ID# 001-4131

Two Position Head Placement.

Universal Body Placement.

May be installed in any position, any orientation.

A

A

B

B

Figure A

1

3

8

" CLEARANCE

3

4

" CLEARANCE

W

A

L

L

Figure C

NOTE: Some power robbing thermostats require the use of
a resistor (always use the resistor provided by the thermo-
stat manufacturer with the Zone Sentry). Consult the ther-
mostat instructions for the resistor installation.

Permitted Angle of Installation on Chilled Water Applications

85

°

85

°

Figure B

L

OCKING

POST

Step 1:
Push in and hold release clip
at the front of the actuator.

Step 2:
Move actuator upward
approximately 3⁄4" to
disengage Locking Posts.

Figure D:    Actuator

                   Removal

CAUTION: Sand or other contaminants can damage
the valves internal components and cause it to fail
prematurely. Precautions must be taken to prevent
contaminants from damaging the valve.

CAUTION:  Actuator  must  be  removed  from  the
valve  body  before  soldering  (see  Figure  D).  Ball
valve must be in the full open position before sol-
dering. Valve shipped in the closed position.

NOTE:  Threaded  valves  (2-way  and  3-way)  should  be
installed using proper plumbing techniques for NPT threads.

Содержание Geo-Sentry V100C3G1ZA024Q4A2

Страница 1: ...uator once or twice and make sure the valve rotates fully 5 Valve body can be submerged for leak testing before the actu ator is attached Actuator Installation Wiring 1 Actuator Removal Remove the valve actuator prior to soldering by pushing in and holding the release clip at the front of the actuator and lifting upward approximately 3 4 see Figure D 2 To re assemble the actuator to the valve body...

Страница 2: ...s the valve body may be installed in any orientation On chilled water installations do not install with the actuator beyond 85 from the topmost position see Figure B 1 Remove actuator from the valve body per previous instructions See Actuator Installation Wiring and Figure D 2 Open the valve to the full open position of the first port to be soldered port A or B 3 Clean and prepare the valve and pi...

Страница 3: ... the thermostat instructions for the resistor installation R C W Y C END SWITCH THERMOSTAT HEAT PUMP GEO SENTRY Field Wiring W Y C END SWITCH THERMOSTAT HEAT PUMP GEO SENTRY Jumper OPTIONAL WIRING DIAGRAM O Y G R O Y G R O Y G C R O Y G Multi status LED and Troubleshooting This troubleshooting table is intended as a helpful guide and is not all inclusive There could be other causes and solutions f...

Страница 4: ...the subject product or part contains no defect as covered in this war ranty the purchaser will be billed for parts and labor charges in effect at time of factory exami nation and repair Any Taco product or part not installed or operat ed in conformity with Taco instructions or which has been subject to misuse misapplication the addition of petroleum based fluids or certain chemical additives to th...