5 Transport and storage
The Topvex SoftCooler should be stored and transported in such a way that it is protected against physical
damage that can harm panels, handles etc. It should be covered so that dust, rain and snow cannot enter
and damage the unit and its components. The appliance is delivered in one piece containing all necessary
components, wrapped in plastic on a pallet for easy transportation.
When transporting the Topvex SoftCooler use a forklift, but once installed on the floor avoid transfer, the
feet can damaged due to lateral loading.
Warning
• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
• Be careful so the unit doesn't tip over.
6 Installation
6.1 Unpacking
Verify that all ordered equipment are delivered before starting the installation. Any discrepancies from the
ordered equipment must be reported to the supplier of Systemair products.
6.2 Where/how to install
Topvex SoftCooler are meant for indoor installation. Place the unit on a
horizontal flat surface
. It’s
important that the unit is completely levelled before it is put into operation.
The electronic components should not be exposed to lower temperature than 0° C and higher than +50° C.
The following max. temperatures applies for an interference-free operation of the Topvex SoftCooler:
• Outside air max. +33 °C
• Extract air max. +28 °C.
• Ambient temperature max. +28 °C.
When choosing the location it should be kept in mind that the unit requires maintenance regularly and that
the inspection doors should be easily accessible. Leave free space for opening the doors and for taking
out the main components (figure 1). General maintenance includes among other things inspection and
cleaning of the drip tray and flange coils.
A floor drain must be available in the room so that the condensation water can be drained off (chapter
6.4.1.3)
Avoid placing the appliance against a wall, as low frequency noise can cause vibrations in the wall even if
the fan noise-level is acceptable. If this is not possible it is recommended to carefully insulate the wall.
Installation instructions
208767
7
Systemair Sverige AB