Moment
Done
Note
Run the compressor for at least 10 minutes.
Then read the Extract-, Outdoor-, Supply and
Exhaust air temperature via the display of the control
unit E28 (in the menu
Temperature
).
Outdoor air temperature__________°C
Supply air temperature___________°C
Extract air temperature __________°C
Exhaust air temperature ____________°C
Let the compressor run.
Measure the hotgas- and liquid line temperature with
a strap-on temperature detector.
Hotgas temperature___________°C
Liquid line temperature_________°C
Keep the compressor running.
Read the below values via the display of the
frequency converter, see section ”Frequency
converter, quick guide”, in Operating and
Maintenance Instructions. First set the parameter for
reading, then let the door of the Topvex SoftCooler
be closed for at least 5 minutes before reading:
• Output frequency (Param d001)
• Output current (Param d002)
• Condenser pressure (Param d004)
Output frequency __________________Hz
Output current ____________________Hz
Condenser pressure ______________bar
Note:
Important! Restore the cooling operation to ”Auto”:
• Log in to the control unit E28 (2222)
• Select menu
Hand/Auto
• Select
Cooler type/coil
• Set Cooler to
Auto
Notes:
Installation instructions
208767
20