5.4 Troubleshooting
Should problems occur, please check or correct the following before contacting your service representative.
Always check if there are any alarms active in the control panel.
1.
Fan(s) do not start
• Check if there are any alarm messages
• Check that the fuses are not defect
• Check the settings in the control panel (times, week schedule, auto/manual operation etc.)
2.
Reduced airflow
• Check the settings for medium and low fan speed
• Check that the outdoor/exhaust air damper (if used) opens
• Check if filters need changing
• Check if diffusers and louvres need cleaning
• Check diffuser/louvre openings
• Check if fans and exchanger block need cleaning
• Check if the roof unit or air intake is clogged
• Check ducts for visible damage and/or build up of dust/pollution
3.
Cold supply air
• Check the control temperature on the control panel
• Check if the overheating thermostat has tripped. If necessary press the red button, marked RESET,
on top of the electrical heater (see figure 3)
• Check if the extract filter must be changed
• Check if the fans have stopped due to overheating. If so the thermal contact might have tripped
(shows as
Fan alarm
in the control panel). If necessary reset (see table 3)
4.
Noise/vibrations
• Clean the fan impellers
• Check that the screws holding the fans are tightened properly
Topvex FR03, FR06, FR08, and FR11
Operation and Maintenance Instructions