Menu Item
Sub-menu
Item
Sub-sub-
menu Item
Explanation
Show and set the digital outputs, output 24V AC.
DO1
: Damper motor on/off. Opens the damper
when the unit is started
DO2
: Not in use
DO3
: Not in use
DO4
: Activates the VVX rotor. Shows the status.
Possible to change the status to:
Auto
,
On
or
Off
. Default is
Auto
.
DO5
: Alarm output. Show the status.
Version
Show the program version
Present version 1.2-1-00.
Configura-
tion
1.
AHU
type
(choose
correct AHU
type)
(Enter into the configuration menu using code
8642)
Fan speed
control
High:
100%
(changeable 0-100%)
Medium:
50%
(changeable 0-100%)
Low:
5%
(changeable 0-100%)
2.
Type
of heater
(choose
correct type
of heater)
3.
Control
parameters
P-band:
30°C
(changeable)
I-Time:
100s
(changeable)
4.
Display
unit type
(E
DSP preset)
5.
Modbus
Comm.
(
Not
Active
or
Active
,
Preset is
Not
Active
)
Modbus:
Active
Modbus address:
7 (changeable)
Speed:
9600 bps (changeable)
Two stop bits: Yes
(changeable)
Parity: No
(changeable)
6.
Modbus-
/ Exoline
Activation
Comm.
Code:
(enter the communication code
given by the supplier of the unit)
7.
Address:
PLA:
254
ELA:
30
Topvex FR03, FR06, FR08, and FR11
Operation and Maintenance Instructions
206575
12
Systemair AB