  GB 

 

 

2.  Checking the heat exchanger (Once a year), (fig. 9) 

After long times use dust may build up in the exchanger and block the airflow. It is vital to 
clean the exchanger regularly to maintain high efficiency. The heat exchanger can easily be 
taken out of the unit. Wash in hot soapy water. Do not use detergent containing ammonia. 
 

Note!  

Make sure that the rotor motor is not exposed to moisture. 

 

3.  Checking the fans (once a year), (fig. 10)

 

Even if the required maintenance, such as changing of filters is carried out, dust and grease 
may slowly build up inside the fans (E and F in fig. 2). This will reduce the efficiency.  
 
The fans may be cleaned with a cloth or a soft brush. Do not use water. White spirit can be 
used to remove obstinate settlements. Allow to dry properly before remounting. 
 
4.  Cleaning extract louvres and inlet diffusers (when  necessary) 
The system supplies fresh air to your home and extracts the used indoor air via the duct 
system and diffusers/louvres.  Diffusers and louvres are mounted in ceilings/walls in 
bedrooms, living room, wetrooms, WC etc. Remove diffusers and louvers and wash in hot 
soapy water as required. (Diffusers/ louvres must not be exchanged which will cause the 
system to be balanced again). 
 

5.  Checking the fresh air intake, (fig. 6)

 

Leaves and pollution could plug up the air intake grille and reduce the capacity. Check the air 
intake grille at least twice a year, and clean if necessary. 
 
6.  Checking the duct system (every 5 years), (fig. 7) 
Dust and grease settlements may build up in the duct system even if filters are changed 
regularly. This will reduce the efficiency of the installation. The duct runs should therefore be 
cleaned/ changed when necessary. Steel ducts can be cleaned by pulling a brush soaked in 
hot soapy water, through the duct via diffuser/ louver openings or special inspection hatches in 
the duct system (if fitted). 
 
NOTE! In addition roof cowl must be checked once a year and cleaned as necessary. 

TROUBLESHOOTING

 

Should problems occur, please check or correct the following before contacting your service 
representative. 
 

1.  Fan(s) do not start

 

Check that all fuses and plugs are connected (mains supply and fan plugs). 
 

2. Reduced airflow

 

a)  Check setting of airflow on control panel. 
b) Change of filter required?  
c)  Cleaning of diffusers/louvers required? 
d)  Cleaning of fans/exchanger block required? 
e)  Is roof unit/air intake clogged? 
f)  Duct system. Check visible duct runs for damage and/or build-up of dust/pollution.  
g)  Check diffuser/louver openings. 

 

8

Содержание TOPVEX-1000 R

Страница 1: ...July 12 TOPVEX 1000 1500 R Compact Air Handling Unit Operating and maintenance instructions GB RU...

Страница 2: ...Fig 1 1 Fig 2 2 B C D E F A G H Fig 3 3 x z Fig 4 4 TOPVEX 1000 R TOPVEX 1500 R x 1180 1480 y 1330 1380 z 750 850...

Страница 3: ...Fig 5 5 Fig 6 6 Fig 7 7 Fig 8 8 Fig 9 9 Fig 10 10 TOPVEX XXX XXXXW XXA 220 240V 50Hz XXXXX XX XX Fig 11 11...

Страница 4: ...ing rooms 7 Extract louvres in wet rooms 8 Soil vent pipe if installed 9 Flexible ducting 10 Spiro ducting 11 Duct insulation Fig 2 A Mains switch B Extract filter C Connection box D Heat exchanger E...

Страница 5: ...anel The units settings is Normal airflow Low at start up Choose Normal airflow High 180V by pressing buttons 13 and 4 simultaneously Setting is confirmed by flashing light in lamp 2 and 3 Normal airf...

Страница 6: ...ths operation time between filter change Lamp 8 for 12 months operation time between filter change Reset operation time after having changed the filter see maintenance section 1 Note The extract filte...

Страница 7: ...to consider the following 1 The system must be installed according to the mounting instructions 2 Insulate mains supply before service or cleaning of the heat recovery unit 3 Tumble dryer must not be...

Страница 8: ...must not be exchanged which will cause the system to be balanced again 5 Checking the fresh air intake fig 6 Leaves and pollution could plug up the air intake grille and reduce the capacity Check the...

Страница 9: ...rotating 4 Noise vibrations a Clean fan impellers b Pull the fans out and check that the 2 screws holding the fans are tightened 5 Alarms Lamps flash as follows Light fig 3 a Short circuit or breach i...

Страница 10: ...RU 10 10 13 13 13 14 15 1 1 2 4 5 6 7 8 9 10 11 2 D F G TOPVEX 1000R H TOPVEX 1500R TOPVEX Systemair 10...

Страница 11: ...RU 3 cde fg hij k 3 4 5 1 2 3 Min 1 Norm 2 180 13 14 2 3 13 5 1 2 Max 3 5 9 10 6 7 8 1 6 2 6 7 3 7 4 7 8 5 8 12 3 11...

Страница 12: ...RU TOPVEX 14 11 6 9 12 9 13 9 13 10 14 6 6 7 9 8 12 1 2 13 3 3 MICRO VATIC VV7592H TOPVEX 1 2 a 1 b c d e 3 PR a 1 b c 2 d c d 12...

Страница 13: ...RU 4 S W a S W b DDMMYY 5 AUTO on off 6 3 7 28 L 30 1 2 3 5 4 5 TOPVEX 3 4 1 1 2 8 Systemair 13 3 5 14 6 7 8 13...

Страница 14: ...RU 2 1 9 3 9 E F 2 4 5 6 6 5 7 1 14...

Страница 15: ...RU 2 a b c d e f g 3 a b 2 c d 2 e 4 a b 5 3 a 6 7 8 14 b 210 6 7 8 6 7 8 14 c 6 8 14 11 15...

Отзывы: