English
ZONE 1 - 2 units
ZONE 2 - 1 unit
ZONE 3 - 2 units
ZONE 4 - 1 unit
ZONE 5 - 3 units
ZONE 6 - 4 units
0110
0110
0110
0110
0101
0101
0101
0100
0011
0011
0010
0001
0001
27
SysHrw
15.12. MOTORISED WATER VALVE
The W/V output on the STORM 2 can be used for a 230 V connection to supply a motorised water valve (the
valve motor capacity must not exceed 250 Watts).
When this valve is installed on the system, it limits main circulation pump energy consumption as well as
limiting the overall pressure losses in the hydraulic circuit.
Initially closed, the valve opens 30 seconds before the compressor starts and closes 20 seconds after it
stops.
It is important that the valve opening time is less than 30 seconds.
The addressing carried out according to the table below means that all the units located in the same area
will receive the same settings.
15.11. µBMS SUPERVISION MODULE
The number of addresses is limited to 15 with a µBMS central supervision unit. The addressing will be
performed using only DIP switches 1, 2, 3 and 4.
Addressing
dip
Zone
1
Zone
2
Zone
3
Zone
4
Zone
5
Zone
6
Zone
7
Zone
8
Zone
9
Zone
10
Zone
11
Zone
12
Zone
13
Zone
14
Zone
15
dip 1
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
dip 2
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
dip 3
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
dip 4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
binary code
0001 0010 0011 0100 0101 0110 0111 1000 1001 1010 1011 1100 1101 1110 1111
Содержание SYSHRW 096
Страница 1: ...Water source heat pump Installation and maintenance manual 22 0 â 30 0kW 27 0 â 38 1kW 096 120 SYSHRW ...
Страница 2: ......
Страница 37: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 38: ...II SysHrw APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...
Страница 40: ...SE 4254 N764 3991287 HRW 96 120 µBMS WIRING DIAGRAM IV SysHrw APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO 096 120 ...
Страница 42: ...VI SysHrw APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...