English
When removing cabinet do not pull or lift it up by the
discharge grilles, to avoid any damages on articulated
fasteners of the access doors.
Caution
100
192
430
G
E
F
D
C
B
A
Ground level
Return
Discharge
condensate
drain pan
M8 fixing screws
4 x 8mm
7
SysCoil Comfort
7.3.2. HN / HC CEILING UNIT
The
HN
/
HC
units are designed for ceiling mounting. Recommended fixing by M8 threaded rod or 8 mm
diameter anchor bolts (contractor supply).
When the
HN
units are ducted at the inlet side, the controller return sensor must be located outside the fan
compartment in order to ensure its good operation.
For the
HC
model with cabinet, it is necessary to remove the cabinet before installing it.
Follow instructions for cabinet removal.
Drill holes in the ceiling in accordance with dimensions mentioned. Install the fixing screws (contractor
supply).
Place the chassis unit on the fixing points and screw it directly to the ceiling, or to the veritable support.
The fan coil unit should be pitched towards the drain side, to facilitate condensate evacuation.
On units with front air intake,
dimension 100 is not required.
Recommended fixing by
M8 threaded rod with H8
hexagonal nut or 8 mm
diameter anchor.
7.4. CABINET REMOVAL
On the
VC
and
HC
models, to hang the unit to the wall, it is
necessary to remove the cabinet.
To achieve this:
1.
Remove the fastener screws from the access hatch situated
at the end of the unit, on the electrical connections side.
Size
SCC10
SCC20
SCC30
SCC40
SCC50
SCC60
SCC70
SCC80
A
mm
66.5
66.5
64
64
63
63
63
69
B
mm
428
428
613
798
983
1 168
983
1 168
C
mm
185.5
185.5
184
184
183
183
195
195
D
mm
189
189
374
559
744
929
744
929
E
mm
415.5
415.5
415.5
415.5
415.5
415.5
519
519
F
mm
61
61
61
61
61
61
88
86
G
mm
569.5
569.5
753
938
1 122
1 307
1 121
1 316