English
15
SysCoil Comfort
9.5.1.2.4. ELECTRICAL CONNECTIONS
Connection of the thermostat
TRM-FA
.
Connections should be made according to the diagram (SEE APPENDIX).
Max. cross-sectional area of wires : 2,5 mm2
9.5.1.2.5. WALL MOUTING
²
Remove the thermostat control knob, the screw and the cover.
²
On a flat surface, mount the control panel using plugs and screws.
²
Install the cover, the screw and the thermostat control knob.
9.5.1.2.6. TECHNICAL CHARACTERISTICS
Operating voltage
230V 50Hz
Contact configuration
SPDT
Temperature range
5 to 30°C
Switching current at 230V AC
6A (cos
ϕ
=1) / 3A (cos
ϕ
=0.6)
Switching differential
approx. 0,5 K
Sensor system
< bimetal
Switches
ON / OFF
mode of operation
fan speed
9.5.1.2.7. FINAL OPERATIONS
ADJUSTMENT OF THE TEMPERATURE RANGE
The room thermostat is set in the factory for a minimum temperature of +5°C and a max. temperature of
+30°C.
Two rings are provided inside the knob for reducing the temperature range.
²
Example: 12°C to 25°C.
ADJUSTMENT PROCEDURE
1.
Setting the temperature range
e.g. max. 25°C, min. 12°C.
2.
Remove the control knob.
3.
Use a pointed object to align the mark on the red ring (max. value) with the desired maximum
temperature (25°C), turning the red index opposite the outside numbers counterclockwise.
4.
Use a pointed object to align the mark on the blue ring (min. value) with the desired minimum
temperature (12°C), turning the blue index opposite the inside numbers clockwise.
5.
Install the control knob.
The temperature ranges can be graduated in:
²
degrees Celsius °C
from 5°C to 30°C
²
number 1 to 6
1=5°C
2=10°C
3=15°C
4=20°C
5=25°c
6=30°C