Valve actuator for 0...10 V control signal

S-RVAZ4-24A is intended to be used together with Systemair’s valves 

ZTV and ZTR.

Technical data

Supply voltage 

 

24 V AC ±15 % 

 

Control signal 

 

0...10 V DC 

Power consumption  

Max 6 watts

Stroke 

 

5.5 mm

Stroke time  

 

30 s

Force  

 

400 N

Ambient temperature, operation   0°C…50°C
Media  temperature  

1°C...110°C

Storage temperature  

-10°C…+80°C

Ambient humidity    

Max 95 % RH

Measurements (W x H x L) 

60 x 75.5 x 92 mm 

Protection class   

IP44

Mounting

The valve should be mounted so that the drive rod on the actuator is 

within 90° from the vertical line and the motor housing is on top. The 

valve actuator’s drive rod should be in its highest/innermost position when 

it is mounted on the valve. 

Fix the actuator to the valve using the connection nut, manual power is 

sufficient.

90º

90º

Wiring

The actuator has a connection cable with a connector which is intended 
for connection to the bottom of the actuator. There is only one way to plug 
in the contact. Be careful not to damage the cable if the connector needs 
to be removed from the actuator.
Connect the supply voltage and control signal. If the actuator and control-
ler share a transformer, it is very important to keep the phase separate 
from the zero, so the same pole is used as zero for both controller and 
actuator, since this is the reference for the control signal.

Red = control signal 0...10 V
Black = 24 V AC (G) (+)
Blue = system neutral (G0) (-) 

Controller,  0...10 V output

Control signal (0...10 V)
Supply voltage (G)
System neutral (G0)

RED

BLACK

BLUE

S-RVAZ4-

24A

Manual manoeuvring

To set the valve position manually, hold down the disengagement button 
(A in the picture below) and then turn the knob for manual manoeuvring 
(B in the picture below) to the desired position. When the knob is turned 
clockwise, the drive rod is pushed outwards and when the knob is turned 
anti-clockwise, the drive rod is pulled inwards. We recommend that the 
supply voltage is cut before the actuator is set manually.

A

B

Position indication

S-RVAZ4-24A has a clear position indication which is shown on the 
knob for manual manoeuvring. There are markings for 0, 25, 50, 75 
and 100 % open position.  

Automatic calibration 

S-RVAZ4-24A has an automatic calibration function for adjustment of 
zero point and stroke in order to adjust the 0...10 V control signal to 
the valve. Calibration takes place each time power is connected.

EMC compatibility

This product conforms with the EMC requirements of European 
harmonised standards EN60730-1:2000 and EN60730-2-8:2002 and 
carries the CE mark.

Contact

Systemair AB, 739 39 Skinnskatteberg, Sweden 
Tel: +46 222 440 00, Fax: +46 222 440 99 
www.systemair.com, [email protected]

S-RVAZ4-24A

8268E

 

SEP

 13

EN

1