44/48 | User Manual S-BM2 | 202010
202010 | User Manual S-BM2 | 45/48
Recommended Course of Action and Inspection Log as per EN 12 101:
1.
Identification of damper
2. Date of inspection
3. Check actuator wiring for damage
4. Check the wiring of the end switches for damage
5. Check the damper cleanliness and clean where necessary
6. Check the inspection lid, cover tightness
7. Check the blade and sealings and correct and record where necessary (where applicable)
8. Check the damper functionality (open and close) as per the “Smoke Control Damper Functionality Check”
chapter and confirm operation by using the control system, tracking the physical behavior of the damper
and signalization of the end positions, and correct and record where necessary (where applicable).
9.
The damper is part of the SHEVS. Therefore, the complete system must be checked as specified in its operational
and maintenance requirements.
10. Set into the operating position – as per the “Operation Manual” chapter.
11. Record the result into the “Operating Journal” with the name and signature of the Inspection Technician.
Warranty Conditions
For warranty conditions, contact your local Systemair representative.
Functionality of every S-BM2 smoke control damper is tested in the production factory before being shipped.
Before you can install the fire damper, its functionality must be tested as per the
Functionality Check” chapter.
DO NOT INSTALL NON-FUNCTIONING SMOKE CONTROL DAMPERS.
Changes of smoke control damper functionality caused by transport or installation are not reclaimable after installation
(deformation, damages, mechanical damage of the sealing material, foreign objects which may constrain the blade
movement, incorrect handling of the activation mechanism, etc.).