Room unit for control of a Corrigo running a 

ventilation application

ED-RU-DFO is an external room unit primarily intended for control 
of an air handling unit via a Corrigo controller running a ventilation 
application. A Corrigo with 2 ports is required in order to use the unit. 
The room unit is connected to port 2 and can be used together with 
expansion units. The room unit can also be used together with EXO-
compact. This requires advanced knowledge of the EXO system.

Technical data

Supply voltage 

 

24 V AC

Power consumption 

25 mA

Protection class   

IP20

Ambient humidity    

Max. 90 % RH

Ambient temperature 

0...50°C

Storage temperature  

-20...+70°C 

Mounting 

  

On wall or device box 

Display type 

 

Backlit LCD 

Communication  

EXOline

Wiring

ED-RU-DFO is connected to the same supply voltage as the Corrigo 
controller (G and G0). Communication takes place via EXOline and is 
connected to port 2, A and B.

24 V AC

42
43

10
11

A
B

G
G0

A
B

Configuration using E tool

©

The desired contents of the display can be configured using E tool

©

This includes room temperature from the built-in sensor of the room unit 
(factory setting), room temperature coming from the Corrigo, outdoor 
temperature, supply air temperature and extract air temperature. 

   

 
When outdoor temperature has been selected, the outdoor temperature 
symbol is shown in the display. Otherwise, the indoor temperature symbol 
is shown.
To read the temperature from the room unit sensor, “Temperature to 
show in ED-RUD” should be set to “Room temp from the display sensor” 
(default setting).
A class A alarm coming from the Corrigo will cause ”SERVICE” to be 
displayed.

E tool

©

 can also be used to set the extended running time, permitted 

max./min. setpoint adjustment for the setpoint buttons and for view-
ing/applying the setpoint displacement.

The On/Off button

The function of the On/Off button can be configured using E tool

©

.

Setting

Description

No function

Pressing the button has no effect.

On/Off

The button can be used to turn the 
unit off or place it in auto mode

On/off/extended 
running

The button can be used to turn the 
unit off or to force it to run in normal 
speed for a settable duration, after 
which it will enter auto mode.

 
When pressing the On/Off button for 10 s, the air handling unit will 
stop. At the next scheduled start-up it will then start and run in mode 
AUTO.
A press of the button will start the unit, making it run at normal speed 
for the duration set under “extended running” (factory setting 60 min.). 
Thereafter, the unit will enter into auto mode.
The LED indicator on the button shows whether or not the unit is 
presently running. As the unit is starting, it will take a few seconds for 
the indicator to light up.
When the unit is in manual position and has been started from the 
display of the Corrigo or using E tool

©

 or a web page, it cannot be 

started or stopped using ED-RU-DFO.

11642A

 

DEC 14