Product Desctription for Systemair NOVA drive 370

This system is designed and optimized to drive rotary heat exchangers. The system consist of a controller and 3 motor 
models: 3Nm, 90 TYD-M-214, max shaft speed 250rpm. 6Nm, 120 TYD-M-214, max shaft speed 350rpm. 10Nm, 120 
TYD-L-214, max shaft speed 350rpm. All have a minimum shaft speed of 0.2rpm. By external gear wheel it can run 
exchangers from 0.02-20rpm. Control signal 0-10V (Modbus RTU) have an un-linear function to ensure a linear heat 
transfer Extract/supply air. The system has a number of functions directed towards this type of application. Among 
these, rotary guard function to check if exchanger is actually moving, purge function to ensure that the exchanger is 
not getting full of particles when not in operation and many more described in this manual.

Содержание NOVA drive 370

Страница 1: ...Systemair NOVA drive 370 Product Description...

Страница 2: ...have a minimum shaft speed of 0 2rpm By external gear wheel it can run exchangers from 0 02 20rpm Control signal 0 10V Modbus RTU have an un linear function to ensure a linear heat transfer Extract su...

Страница 3: ...Product description 4 3 Environmental constraints 4 4 Technical data 5 5 Mechanical and electrical installation 7 6 Motor parameters 11 7 LED behaviour 12 8 Fault behaviour 12 9 RHC features 13 10 Mo...

Страница 4: ...the electrical installation on the rating plate matches the power supply Please refer to Table 2 for maximum fuse ratings and type CAUTION Risk of hot surfaces and electric shock if the unit has been...

Страница 5: ...utral or phase to phase earth ground Frequency Hz 50 Hz 2 Hz Max input current 230V supply Arms 3 6 External input fuse size Type MAX C16 Minimum supply without speed reduction Vrms 207 Minimum supply...

Страница 6: ...RS485 24V protected Control interface alarm 1x Alarm relay NC C NO Maximum 2A 250Vac or 6A 24Vdc Indicators Red Green Yellow LED on the PCB check Figure 6 for position Settings Dipswitch for Motor se...

Страница 7: ...entation shall be vertical with the cable glands facing downwards This is to ensure the best thermal performance of the product For reference please refer to Figure 2 Figure 2 Mounting orientation of...

Страница 8: ...Motor U V W Supply N L Alarm NC COM NO Solid wire 1 2 0 2 4 0 mm2 26 12 AWG Stranded wire 1 0 2 2 5 mm2 26 14 AWG Flat blade max 3 5 mm Analogue Control 0V Uin Uout Rotary Sensor 0V RUN DIR MODBUS 0V...

Страница 9: ...ing Grounding hazard For the operator safety it is important to ground the drive properly and follow the provided grounding guidelines RCD compatibility For extra safety protection a Residual Current...

Страница 10: ...anner until power is reset Enable rotary guard To use the rotary guard the sensor must be supplied with 10 V from Uout 10V and connected to ground 0V The out put from the sensor must be connected to R...

Страница 11: ...if you wish to change the direction the motor rotates Note that the direction will change the next time the motor starts not when it is already rotating Maximum speed can be reduced and set as 50 100...

Страница 12: ...how the latest error as it has higher priority Rotary guard Rotary guard passed When the rotary guard passes it shows the red green red green sequence 200ms each LED If the inverter has no warnings or...

Страница 13: ...9 for a diagram When the inverter is running the motor and the rotary input is high for more than 10 seconds the functionality is disabled At this point a power reset is needed to enable it again 9 2...

Страница 14: ...owing Modbus registers are available All the registers are either input registers 16 bit read only denoted by R or holding registers 16 bit read write denoted by RW Register Address Type Description B...

Страница 15: ...rd in 0x115 R Rotor guard value 0 or 1 Test running 0x116 R 1 when test is running 0 otherwise Speed external 0 10V 0x117 R 0 4095 speed input Trimmer 0 10V 0x118 R 0 4095 trimmer input Extended SW ve...

Страница 16: ...Safety req Automatic electrical controls for household and similar use EN 60335 2 40 2004 A11 2014 A12 2005 Safety req Particular requirements for electrical heat pumps air conditioners and dehumidifi...

Страница 17: ...286rpm Current 0 79 0 46A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 2 8 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation...

Страница 18: ...ent 1 37 0 79A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 5 5 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation direction...

Страница 19: ...rent 2 04 1 18A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 8 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation direction C...

Страница 20: ...no www systemair no Systemair B V Zanddonkweg 7a 5144 NX Waalwijk NETHERLANDS Tel 31 0 85 00 66 200 info systemair nl www systemair nl Systemair HVAC Spain S L U C Montecarlo 14 Fuenlabrada ES 28942...