The place of installation must be designed in accordance with
the valid building regulations, paying particular attention to the
specific functions of the installed technical systems.
n
The place of installation must be secured in accordance with
the local regulations to prevent personnel and materials from
falling.
n
For protection from water damage, the floor at the installation
site must be sealed off from any rooms below it and must be
equipped with a sufficiently dimensioned floor drain.
n
The location for erection must meet with the constructional
requirements for statics and acoustics.
n
Never use the device as any part of the building structure or as
part of the building's roof.
n
The ground must be even and horizontal so that device is
placed as flat as possible.
n
In order to ensure fault-free operation, the device has to be
aligned horizontally over the entire device surface.
n
The foundations must be designed to support the weight of the
device.
n
For units fitted with the optional adjustable feet, these may be
adjusted to aid with levelling the unit.
n
Sound transmission between the unit base frame and the foun-
dations must be prevented.
If the installation site is in the Ex-protected area, the device must
comply with ATEX requirements.
n
In accordance with the hygiene requirements in DIN 1946,
Part 1, the device must be easy to access at all times without
having to enter room air class 1.
n
When used for operating theatres the unit should preferably
be installed one floor above or in the immediate vicinity of the
operating theatres it is serving.
3.2.2 Additional requirements for outdoor units
n
The cabling between the device and the external control cab-
inet must be laid properly and take into consideration external
influences such as rain, snow, wind and direct sunlight.
n
All cable runs and associated device components must be
frost-proof and installed taking external influences, such as
rain, snow, wind and direct sunlight, into consideration.
n
If the design includes an operator walkway, then it must be
frost-proof and equipped with suitable heating system.
n
Comply with the maximum permitted roof loads and external
influences such as rain, snow, wind and direct sunlight.
n
A sealing layer of rubber has to be applied between the device
base and the on-site base.
Foundation of the place of installa-
tion
Additional requirements for use in
an explosion-risk area
Additional requirements for use in
the health system
On-site requirements > Additional requirements for outdoor units