MAXK

Installation and Operating Instructions

GB

Содержание MAXK Series

Страница 1: ...Document in original language MAXK Installation and Operating Instructions GB...

Страница 2: ...air AB All rights reserved E OE Systemair AB reserves the rights to alter their products without notice This also applies to products already ordered as long as it does not affect the previously agree...

Страница 3: ...indications for the kind of delivery dismantled assembly group 9 6 5 1 Unit profile 9 6 6 Mounting indications for wet parts 10 7 Internal components 10 7 1 V cell filter 10 7 2 Air heater air cooler...

Страница 4: ......

Страница 5: ...Declaration of Incorporation 1 1 Declaration of Incorporation...

Страница 6: ...Carry out this action 1 Carry out this action if applicable further actions 2 Carry out this action 3 if applicable further actions 2 2 Notes on the documentation Warning Hazard as a result of improp...

Страница 7: ...system Take care not to damage the water battery when connecting water pipes to connectors Use a spanner to tighten the connection 4 Product information 4 1 General This installation manual concerns a...

Страница 8: ...for application in residential construction At an external pressure of Pa 190 Also suitable for application in residential construction Effective heat recovery rate 84 84 84 84 84 87 Electric power co...

Страница 9: ...B A 63 6 78 3 63 6 61 8 79 6 Operation at the upper limit 5 Transport and storage 5 1 General MAXK I3 DC air handling units are delivered in transport units The width of the lorry inside width approx...

Страница 10: ...Use only forks which extend to the whole width of the single parts Note lenght of fork width of equipment approx 100 mm Too short forks cause damages at the range of the floor covering 5 4 Big units S...

Страница 11: ...rning The devices have to be adjusted to vibration elements Mafund Asozell Silomer a s o to avoid a transmission of structure borne noise and to guarantee the ventilation of the device base floor The...

Страница 12: ...guaranteed Thus the function of the devices is guaran teed and leakages at doors or device connections are prevented Step 1 Check the mounting surfaces as to their planeness Unplane mounting surfaces...

Страница 13: ...ndications for the kind of delivery dismantled assembly group Kind of delivery delivery of devices partially screwed resp completely dismantled Before plugging on the device profiles the stops of the...

Страница 14: ...pollution must be controlled with a differential pressure device U tube inclined tube Filter cells have to be renewed completely after the maximum difference pressure has been reached Check the stand...

Страница 15: ...the piping General rule for Cu Alu register The water forerun has to be connected on that collector which is situated very close to the air outlet Attention In case of mounting the connection must be...

Страница 16: ...s a minimum of wear On heaters with higher ratings part of the output are controlled by a step controller However fine adjustment of the temperature is always carried out by the electronic ON OFF cont...

Страница 17: ...ors at pressure side release chains only after standstill of the ventilators 7 8 Silencer To avoid fan noise being transferred via the duct system silencers should be installed both on supply and extr...

Страница 18: ...ents and rubber sleeves are automatically delivered parts 1 to 5 The syphon may not be connected directly with a drain conduction but it must be guaranteed that it can run out freely Before putting in...

Страница 19: ...wing of the tub is preprogrammed 8 1 Syphon for cooler Pressure operation Note For tubs which have to be connected within the overpressure range hand made syphons must be installed These must have a r...

Страница 20: ...e weather protection roof cannot be bought immediately the top of the unit must be covered watertight The outside joints of outdoor units have to be permanently elastic sealed While assembly work the...

Страница 21: ...t roof frame insulated extra charge detail drip ledge Mounting of the drip ledge install set up bolt the device screw the drip ledge with a drilling screw 4 8 x 19 at the device brace Mount pre fabric...

Страница 22: ...east 150 mm Caution If the unit is installed in a cold place make sure that all joints are covered with insulation and tape well Duct connections duct ends should be covered during storage and install...

Страница 23: ...amage is caused due to your failure to observe these instructions the guarantee is invalidated 11 3 Maintenance instructions Performance Component Activity Periodic If required Number per year 1 Fan 1...

Страница 24: ...e filter and document the filter change x 8 Weather protection guard 8 1 Examine for dirt mounting damage and corrosion x 1 8 2 Function sustenance cleaning x 9 Damper 9 1 Examine for dirt damage and...

Страница 25: ...om the power supply and contact the manufacturer Fan running roughly unsteady Imbalance of the impeller Rebalancing by spcialized company Wrong direction of rotation of the impeller Consultation with...

Страница 26: ...defect Contact the manufacturer Air handling unit does not cool or cools insufficiently Air in the water cooling battery Venting To high temperature of the cooling coil Control the temperature of the...

Страница 27: ......

Страница 28: ...MAXK Installation and Operating Instructions en_GB 2017 06 13 Systemair GmbH Seeh fer Str 45 97944 Boxberg Germany Tel 49 0 7930 9272 0 Fax 49 0 7930 9273 92 info systemair de www systemair de...