INSTRUCTIONS FOR  

 

WATER COOLER ACTIVATION

 

CORRIGO CONTROLLER 

 

 

Basic 

FGT010, FGT015, FGT022 

 

 

 

Содержание CORRIGO

Страница 1: ...INSTRUCTIONS FOR WATER COOLER ACTIVATION CORRIGO CONTROLLER Basic FGT010 FGT015 FGT022 ...

Страница 2: ... 3 Search for type of cooler menu 7 4 Electric wiring diagram 8 5 In case that your FGT Basic unit will not have any heater element 9 5 1 Deactivating frost protection sensor 10 5 2 Deactivating heating signal AO 12 5 3 Deactivating heating signal DO 13 5 4 Change type of heater element 14 ...

Страница 3: ... 1 Search for Admin access Put yourself on the first screen Press DOWN key button to enter the menu Press DOWN key button 4x to access the menu Access rights Press RIGHT key button Press RIGHT key button ...

Страница 4: ...rself on Enter password Please enter the password 1111 For entering the password press UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 Press OK button and you will be logged in as Admin ...

Страница 5: ...ler Press LEFT key 2x to get to the menu Press UP key button to position yourself on the menu Configuration Press RIGHT key button Press RIGHT key button Press DOWN 7x to get to AO Press RIGHT key button In the top left corner the menu will show AO1 ...

Страница 6: ...to change from Not used to Y3 cooling To do that you need to press DOWN key 3x and OK button 3x Now we selected the signal for cooling We need to select what type of water cooler we have After activating the function you must restart the unit ...

Страница 7: ...efore Press LEFT key 2x for menu Inputs Outputs Press DOWN key button 8x for menu Cooling Press RIGHT key button Press OK button and then UP key 2x for Water and again OK button to confirm Configuration for water cooler is completed Press LEFT 2x Press UP key 7x to return to main screen ...

Страница 8: ...8 4 Electric wiring diagram ...

Страница 9: ...ic unit will not have any heater element If FGT Basic AHU will be only for cooling request without any heater element it is necessary to deactivate frost protection sensor signal for relay activate and type of heating element Put yourself on the first screen Press DOWN key button to enter the menu Press DOWN key button 4x to access the menu Access rights Press RIGHT key button ...

Страница 10: ...sword Press UP key 2x for value 1 Press RIGHT key for next position and repeat the process for the password 1111 Press OK button and you will be logged in as Admin 5 1 Deactivating frost protection sensor Press LEFT key button 2x to get to the menu Press UP key button to position yourself on the menu Configuration Press RIGHT key button ...

Страница 11: ...n 5x to put yourself to menu UI exp3 Press RIGHT key button On the top left of the screen you should have UI1 selected Press DOWN key for UI2 We need to change the Frost prot t to Not used Press OK button and then UP key 11x and again OK button 2x ...

Страница 12: ...12 5 2 Deactivating heating signal AO Press LEFT key button Press DOWN key button 2x Press RIGHT key button Press OK to change value from Y1 heating to Not used Press UP key button Press OK button 3x ...

Страница 13: ... 3 Deactivating heating signal DO Press LEFT key button Press DOWN key for menu DO Press RIGHT key button We need to change from P1 heating to Not used Press OK button and then UP key 5x Press OK button 2x ...

Страница 14: ... top menu shown one step before Press LEFT key 2x for menu Inputs Outputs Press DOWN key 6x for menu Heating Press RIGHT key button Now press OK button and UP key button 2x Menu should be displayed Not connected and press OK button Configuration for Electric heater is complete Press LEFT 2x Press UP key button 7x to return to main screen ...

Отзывы: