26 SYSAER R32
12.2.2. WIRING DIAGRAM KEY DESCRIPTIONS
12. WIRING DIAGRAM AND LEGEND
12.1. WIRING DIAGRAM
SEE APPENDIX
12.2. LEGEND
12.2.1. POWER SUPPLY
The supply is protected at the head by an FFG main fuse holder supplied by the installer. It must be fitted
next to the unit. Refer to the §
ELECTRIC SPECIFICATIONS
, page 15
The electrical installation and wiring of this unit must comply with local electrical installation standards.
²
Three phase 400 V~ 50Hz + Ground :
On the L1, L2, L3 terminals of the QG section switch
On the ground screw of the earth cable.
Power cable must be connected to the main power supply switch QG (Copper cable is recommended).
SE4903
Models SR R32 105 and SR R32 140
Power
400V / 3~ / 50Hz ± 10%
SE4903
Gas detection module
Control
230V / 50Hz ± 10%
SEE APPENDIX
12.2.3. RANGE AND SETTINGS OF THEMAL PROTECTION / NOMINAL INTENSITY OF THE CONTACTORS
(CLASSE AC3)
MODELS
SR R32 105
SR R32 140
FTI
Range
30-40A
37-50A
Adjustment
38A
48A
FT2
Range
30-40A
37-50A
Adjustment
32A
48A
FT5
EC motor
14A
18A
FT6
FT7
Range
2.5-4A
2.5-4A
Adjustment
4A
4A
FT13
Range
14A
14A
Adjustment
17-23A
17-23A
FT8 EC motor
21.6A
21.6A
FTC
2A
2A
FFT
1A
1A
FFT4
1A
1A
Contactors
K1
40A
50A
K2
40A
50A
K6/7
6A
6A
K13
25A
25A
12.2.3.1. SYSAER R32 WITH STANDARD FAN
N 819