46/64 |
F-B90
Electrical connections
WARNING
• Risk of electric shock.
• Stop the power supply before you do work on electrical equipment.
• Only approved electricians can do work on the electrical system.
To access the electrical parts of this product follow instructions in "Product Handling" section.
Electrical parameters for type of activation and actuator
F-B90 (B230T … BSD24T)
T | NVF |
PC | A
W (mm)
150 175 200 225 250 280 300 315 350 355 400 450 500 550 560 600 630 650 700 710 750 800
H
(
m
m
)
250
375
500
625
750
875
1000
B230T | AC 230 V, 50/60 Hz | 6,5 VA | BFL230-T
B24T | AC (50/60 Hz)/DC 24 V | 4 VA | BFL24-T
BST0 | AC 230 V, 50/60 Hz | 11 VA | BFL24-T-ST + BKN230-24
B24T-SR | AC (50/60 Hz)/DC 24 V | 6,5 VA | BFL24-SR-T
BSD230T | AC 230 V, 50/60 Hz | 11 VA | BFL24-T-ST + BKN230-24-C-MP + ORS144K
BSD24T | AC 230 V, 50/60 Hz | 6 VA | BFL24-T + ORS144K
B230T | AC 230 V, 50/60 Hz | 10 VA | BFN230-T
B24T | AC (50/60 Hz)/DC 24 V | 6 VA | BFN24-T
BST0 | AC 230 V, 50/60 Hz | 11 VA | BFN24-T-ST + BKN230-24
B24T-SR | AC (50/60 Hz)/DC 24 V | 8,5 VA | BFN24-SR-T
BSD230T | AC 230 V, 50/60 Hz | 11 VA | BFN24-T-ST + BKN230-24-C-MP + ORS144K
BSD24T | AC (50/60 Hz)/DC 24 V | 8 VA | BFN24-T + ORS144K
B230T | AC 230 V, 50/60 Hz | 11 VA | BF230-T (BF230-TN-2)
B24T | AC (50/60 Hz)/DC 24 V | 10 VA | BF24-T (BF24-TN-2)
BST0 | AC 230 V, 50/60 Hz | 11 VA | BF24-T-ST (BF24-TN-ST) + BKN230-24
B24T-SR | AC (50/60 Hz)/DC 24 V | 9,5 VA| BF24-SR-T (BF24-SR-TN)
BSD230T | AC 230 V, 50/60 Hz | 11 VA | BF24-T-ST (BF24-TN-ST) + BKN230-24-C-MP + ORS144K
BSD24T | AC (50/60 Hz)/DC 24 V | 11 VA | BF24-T (BF24-TN-2) + ORS144K
Содержание 178818
Страница 1: ...F B90 Multiblade Fire Damper Handbook...
Страница 21: ...21 64 F B90 5 1 1 2 B A1 A2 3 A1 B A2...
Страница 22: ...22 64 F B90 C1 C2 C3 C4 C5 i D 4 1 8 1 Fx D1 D2...
Страница 23: ...23 64 F B90 F3 5 2 E F F3 E1 E2 5 F1 F2 6...
Страница 48: ...48 64 F B90 Wire preparation C1 A1 A2 B C2 C2 H B G A1 A2 B 2 1 C2 C1...
Страница 61: ...61 64 F B90 D1 D2 D3 P13 P13 E E H B G 1 2 H...
Страница 64: ...Systemair DESIGN 2021 08 25 Handbook_F_B90_en GB...