29
Rev. 04GB1410
SYSTEMA S.p.A.
EOLO BLULINE
1 2
MFO
EP
C OP
3 4 P1
K1
C
P2
K2
C
P3
K3
C
P4
K4
C
+A
S
-B
P4
P
K
C
P3
P
K
C
P2
P
K
C
P1
P
K
C
2.6
CONNECTION DIAGRAM OF THE ELECTRIC CONTROL BOARD OF INET NET-
WORK WITH THE ZONE PROBES FOR ONE OR MORE COMBUSTION GROUPS
LEGEND PROBES CONNECTIONS
P1-P2-P3-P4
INET from 1 to 16 units - 1 Thermal zone
Code: 94CECR2695
P1
Internal probe
C
Common
K1
Key selector
INET 16 units - 2 thermal zones
Code: 94CECR2696
ZONE1:
P1
Internal probe
C
Comune
K1
Key selector
ZONE2:
P2
Internal probe zone2
C
Common zone2
K2
Key selector zone2
INET 16 units - 3 thermal zones
Code: 94CECR2697
ZONE1:
P1
Internal probe
C
Common
K1
Key selector
ZONE2:
P2
Internal probe zone2
C
Common zone2
K2
Key selector zone2
ZONE3:
P3
Internal probe zone3
C
Common zone2
K3
Key selector zone3
INET 16 units - 4 thermal zones
Code: 94CECR2698
ZONE1:
P1
Internal probe
C
Common
K1
Key selector
ZONE2:
P2
Internal probe zone2
C
Common zone2
K2
Key selector zone2
ZONE3:
P3
Internal probe zone3
C
Common zone3
K3
Key selector zone3
ZONE4:
P4
Internal probe zone4
C
Common zone4
K4
Key selector zone4
LEGEND INET CONNECTIONS (all models)
1-2
Power supply (230VAC 50/60Hz)
3-4
Alarm relay 3(1) A 230Vac (only for preset models)
C-OP
External probe (only for preset models)
+A, -B, S
BUS INET network connections
Connection probes
P1-P2-P3-P4
Twisted cable shielded
and separated from the
cables of power supply,
min. 3x0,5 mm
2
.
USE OF THE KEY SELECTOR (WHEN PRESENT):
It is used to interact directly with the electric board, giving the choice of 3 differ-
ent functioning modalities:
AUTO = The timer is executing the programs which have been preset for the
selected zone
OFF =
The timer is excluded and, for the selected zone, the security setpoint
rt is maintained (if enabled)
ON =
The timer is excluded and, for the selected zone the setpoint SP1 is
maintained
ELECTRICAL CONNECTIONS PROBES: Avoid to cross the cables, separating
the very low tension connections from the network connections. The cable for the
connection of a probe must have a section lot lower than 0,5 mm
2
and its length
is limited to 10 m. In case of connections longer than 10 m it is recommended the
use of shielded cable, taking care to connect the shielding to the common con-
nection of the inlet of the probe of thermostat or of the remote control.
Fig 2.3