I56-0003-001 

 

 01-12

For use with the following models: 
Wall Speakers: SPSWL-ALERT

PRODUCT SPECIFICATIONS

Standard Operating Temperature:

32°F to 120°F (0°C to 49°C)

Humidity Range:

10 to 93% Non-condensing

Nominal Voltage (speakers):

25 Volts or 70.7 Volts

Maximum Supervisory Voltage: 

50 VDC

Speaker Frequency Range: 

400 – 4000 Hz

Power Settings: 

¼, ½, 1, 2 Watts

Input terminal wire gauge:

12 to 18 AWG

Strobe Flash Rate: 

1 flash per second

Nominal Voltage (strobes): 

Regulated 12VDC, regulated 24VDC or FWR

Operating Voltage Range (includes fire alarm 
panels with built in sync): 

8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)

Operating Voltage with MDL3 Sync Module: 

8.5 to 17.5V (12V nominal) or 16.5 to 33V (24V nominal)

DIMENSIONS FOR PRODUCTS AND ACCESSORIES

MOUNTING BOX OPTIONS

WALL PRODUCTS

Length

Width

Depth

SPEAKER STROBES

Wall Speaker Strobe

6.5" (165 mm)

5.00" (127 mm)

2.30" (58.4 mm)

4" x 4" x 2

1

/

8

" or deeper,  

SBBSPRL/WL (wall)

WALL SURFACE MOUNT BACK BOX 

Length

Width

Depth

Speaker Strobe with SBBSPRL/WL Surface 
Mount Back Box

6.62" (168mm)

5.12" (130 mm)

2.30" (58.4mm)

NOTICE:

 This manual shall be left with the owner/user of this equipment.

BEFORE INSTALLING

Please read the System Sensor Voice Evacuation Application Guide, which 
provides detailed information on speaker notification devices, wiring and 
special applications. Copies of this manual are available from System Sensor. 
NFPA 72 and NEMA guidelines should be observed. System Sensor also rec-
ommends installing fire alarm speakers in compliance with NFPA 72, ANSI/
UL 1480 and NEC 760

Important: 

The notification appliance used must be tested and maintained 

following NFPA 72 requirements. 

GENERAL DESCRIPTION

System Sensor series of notification appliances offer a wide range of audible 
and visible devices for life safety notification. Our indoor speaker strobes 
come with 7 field selectable candela setting. The strobe portion is designed 
to be used in 12 VDC, 24VDC, or 24V FWR (full wave rectified) systems. The 
speaker is designed to be used at either 25 or 70.7 volts, and operate at any 
one of four input power levels. Our speaker strobes are suitable for dry and 
damp environments. These products are electrically backwards compatible 
with previous generation of System Sensor speaker strobes. With its low total 
harmonic distortion, the System Sensor SPL series offers high fidelity sound 
output. 

System Sensor amber lens ALERT Speakers Strobes are private mode notifica-
tion appliances intended to alert trained personnel to investigate a life safety 
event. The speaker is listed to ANSI/UL 1480 (public mode) and the strobe is 
listed to ANSI UL 1638 (private mode). 

FIRE ALARM SYSTEM CONSIDERATIONS

System Sensor also recommends installing fire alarm speakers in compliance 
with NFPA 72, ANSI/UL 1480 and NEC 760. 

SYSTEM DESIGN

The system designer must make sure that the total current drawn by the de-
vices on the loop does not exceed the current capability of the panel supply, 

and that the last device on the circuit is operated within its rated voltage. The 
current draw information for making these calculations can be found in the 
tables within this manual. For convenience and accuracy, use the voltage drop 
calculator on the System Sensor website (www.systemsensor.com).

When calculating the voltage for the last device, it is necessary to consider 
the voltage drop due to the resistance of the wire. The thicker the wire, the 
smaller the voltage drop. Note that if Class A wiring is installed, the wire 
length may be up to twice as long as it would be circuits that are not fault 
tolerant. The total number of strobes on a single NAC must not exceed 69 for 
24 volt applications. 

AVAILABLE CANDELA SETTINGS

System Sensor offers a wide range of candela settings for your life safety 
needs. In order to select your candela output, adjust the slide switch on the 
rear of the product to the desired candela setting on the selector switch. (See 
Figure 1.)

The candela setting can also be verified by looking into the small window on 
the front of the unit. See Table 1 for candela settings for wall products. All 
products meet the light output profiles specified in the appropriate UL Stan-
dards. (See Figures 2 and 3.)

For amber lensed strobes used for full profile measurement, listed candela rat-
ings must be reduced in accordance with Table 2.

FIGURE 1. CANDELA SELECTOR 

 

  

A0486-00

CURRENT DRAW RATINGS

For the strobe, the current draw for each setting is listed in Table 1.

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630/377-6495

www.systemsensor.com

I56-000

3-00
1

Selectable Output Amber Lens ALERT 

Speaker Strobe – Wall Mount