background image

D900-43-00 

 

I56-282-000R

INPUT FROM

AMPLIFIER

TO NEXT

SPEAKER OR EOL

A075-00

2. See Figure 2 as an example of how to select a 

/

4

 Watt input 

when a 25 volt amplifier is being used. Notice that the header, 
SW, has two shunts. One shunt is used to select either 25 or 
70.7 volts input. The other shunt is used to select input power 
of 

/

4

/

2

,  or 2 Watts.

Figure 2:

25.0V

70.7V

2W

1W

1/2W

1/4W

25.0V

70.7V

2W

1W

1/2W

1/4W

CORRECT

SW1

SW
1

INCORRECT

A002-00

Specifications

Mechanical

Input Terminals: 

2 to 8 AWG

Speaker Size: 

4 inches (0 mm)

Grille Size 

   

 

   Round: 

7

/

8

 (87 mm)

   Square: 

7

/

8

 (27 mm)

Electrical

Voltage Input: 

25 volts or 70.7 volts (nominal)

Maximum Supervisory Voltage:  50 VDC
Frequency Range: 

400 – 4000 Hz

Operating Temperature Range: 

32° to 20°F (0° to 49°C)

Power: 

/

4

/

2

,  and 2 Watts

Listings: 

UL S4048

Storage Temperature: 

–20°C to 70°C

Operational Humidity Range: 

10 

 93% RH (non-condensing)

NOTE:  

The SP300 Series is suitable for dry and damp environments. Not suitable for use in air handling spaces.

General Description

The  National  Fire  Protection  Association  (NFPA)  has  published 
standards and recommended practices for the speakers described 
in  this  manual.  As  a  result,  the  installer  must  be  familiar  with 
these requirements as well as all local codes and special require-
ments of the authority having jurisdiction.

SP300 series speakers can be operated with distribution amplifiers 
having an output voltage of either 25 volts or 70.7 volts.

The speakers operate at any one of four input power levels. The 
output sound level is selected at the time of installation, but can 
be changed, if necessary.

The speaker is also equipped with a capacitive input to allow for 
DC supervision.

Installation

All  wiring  must  be  installed  in  compliance  with  the  National 
Electrical  Code  (NEC)  and  applicable  local  codes  as  well  as 
special  requirements  of  the  authority  having  jurisdiction,  using 
the  proper  wire  size.  This  also  includes  all  applicable  NFPA 
Standards, ANSI/UL 480, and NEC 760.

Electrical

. Connect the speaker as shown in Figure . 

NOTE:

  Do  not  loop  electrical  wiring  under  terminal  screws. 

Wires  connecting  the  device  to  the  control  panel  must 
be broken at the device terminal connection in order to 
maintain electrical supervision.

3825 Ohio Avenue, St. Charles, Illinois 6074

800/736-7672, FAX: 630/377-6495

www.systemsensor.com

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

SpectrAlert SP300 Series
Dual Voltage Transformer Speakers
for Fire Protective Signaling Systems

For use with the following models: SP300W, SP30R, SP30W
U.S. patent number: D424465

NOTICE:

  This manual shall be left with the owner/user of this equipment.

Figure 1. 
Electrical 
connections:

Отзывы: