background image

D440-03-00 

I56-3475-000

RTS151KEYA

Remote Test Station

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 6581 Kitimat Road, Unit 6, Mississauga, Ontario L5N-3T5

1-800-SENSOR2, FAX: 905-812-0771

www.systemsensor.ca

NOTE: RTS151KEYA replaces RTS451KEYA.

NOTICE: This manual shall be left with the owner/user of this equipment.

NOTE: A test coil is required only for use with D2A,DNRA,DH400A,DH500A 

models.  For  D2A  models  order  part  #  DCOIL.  For  DH400A/500A    models 

order part #Coil.

GENERAL INFORMATION

The  System  Sensor  RTS151KEYA  is  an  automatic  fire  detector  accessory 

designed to test remotely located duct and beam detectors. For 4-wire detec-

tors, the RTS151KEYA features a multi-colored LED that alternates between 

steady green and red. Green indicates power and that the detector board is 

in place. Red indicates alarm. For 2-wire detectors, the LED will show red for 

alarm. Consult the detector installation instructions for additional information.
The National Fire Protection Association and CAN/ULC-S536 has published 

codes,  standards,  and  recommended  practices  for  the  installation  and  use 

of this product. It is recommended that the installer be familiar with these re-

quirements, with local codes, and any special requirements of the local au-

thority having jurisdiction.

RTS151KEYA CONTENTS

1 RTS151KEYA remote test station
1 screw pack (2 mounting screws)
2 Keys

OPERATION

Test Function

Insert the key and turn clockwise to the “TEST” position.

Alarm Indication

With the key in the “TEST” position, some time will elapse (40 seconds maxi-

mum) depending on the detector type, before the alarm indicating LED will 

turn red.

Reset Function

Turn the key counterclockwise to the “RESET” position and hold. The LED 

should turn off. Then, turn the key back to the “NORMAL” position and re-

move. The RTS151KEYA is capable of resetting only certain models of detec-

tors. Refer to the detector installation instructions for additional information.

Wiring Instructions

Consult  the  appropriate  detector  installation  instructions  for  the  applicable 

wiring diagram. The RTS151KEYA mounts to a single gang box (2 

1

/

2

˝ mini

-

mum depth), or directly to the wall or ceiling.
In Canadian applications, the RTS151KEYA is intended to be located in the 

same room as the smoke detector and within 60 feet of the unit.

OFF

RESET

TEST

H0195-01

H0582-13

FIGURE 1. RTS151KEYA

FIGURE 2: WIRING DIAGRAM FOR RTS151KEYA TO D4120A 

4-WIRE DUCT SMOKE DETECTOR:

FIGURE 3: WIRING DIAGRAM FOR RTS151KEYA TO D2A 2-WIRE 

DUCT SMOKE DETECTOR:

SPECIFICATIONS

Dimensions: 

4.6˝ H × 2.75˝ W × 1.8˝ D

Weight: 

0.24 Lbs.

Power Requirements

     Power LED (Green): 

14 – 35 VDC, 12 mA maximum

     Alarm LED (Red): 

2.8 – 32 VDC, 12 mA maximum

Alarm Response Time: 

40 seconds maximum

Temperature: 

–10°C to 60°C (14°F to 140°F)

Humidity: 

95% relative humidity, noncondensing Max

2

6

1
5

4

3

D4120A

RTS151KEYA

(GREEN LED) 

POWER

(RED LED) 

ALARM

FIELD 

INSTALLED 

JUMPER

AUX OUT +

AUX OUT –

ALARM

R TEST
R RESET

SUP, NO
SUP, C

* Sup. contacts cannot be used if they are wired to control panel.

*

EXTERNAL

(-) POWER (+)

SUPPLY

*

RTS151KEYA

REMOTE TEST STATION

LED OPTION

1 PER UNIT

10mA CURRENT DRAW

TEST COIL OPTION

1 PER UNIT

95mA CURRENT DRAW

4

5

3

2

1

TEST COIL +

TEST COIL –

COMM +

OUT (CONV ONLY) +

COMM –

RA/RTS –

RA +

RTS +

NOTE:

 THE RTS151KEYA TEST COIL 

CIRCUIT REQUIRES AN EXTERNAL 24 VDC 

POWER SUPPLY WHICH MUST BE UL LISTED.

NOTE:

 THE USE OF A REMOTE TEST STATION REQUIRES THE 

INSTALLATION OF AN ACCESSORY COIL, PART NUMBER DCOIL, 

SOLD SEPARATELY.

H0571-10