SPECIFICATIONS

Wire Gauge for Terminals:

22 AWG (0.64 mm, 0.34 mm²) to 14 AWG (1.6 mm, 2.08 mm²)

Operating Voltage Range:

Without isolator: 15 to 32 VDC
With isolator: 15-28.5V

Maximum Standby Current:

13 mA @ 32 VDC, 20 mA @ 15 VDC

Maximum Alarm Current (LED on):

22 mA @ 32 VDC, 22 mA @ 15 VDC

Operating Humidity Range:

0% to 95% Relative Humidity, Non-condensing

Operating Temperature Range:

–4°F to 131°F (-20°C to +55°C).
UL-Listed for use from 32°F to 100°F (0°C to 37.8°C)

Adjustment Angle:

20 degrees vertical, 50 degrees horizontal

Sensitivity Levels:

Level 1 25%, Level 2 30%, Level 3 40%, Level 4 50%

Fault Condition (Trouble):

Long-term drift reference out of 20% range, beam blockage or detector out of alignment, imager saturated

Alignment Aid:

LED directional arrows

Alarm Indicator:

Local red LED and remote output

Intellectual Property and Copyright

This document includes registered and unregistered trademarks. All
trademarks displayed are the trademarks of their respective owners.
Your use of this document does not constitute or create a license or any
other right to use the name and/or trademark and/or label.

This document is subject to copyright owned by HPSS (Honeywell
Products & Solutions Sarl). You agree not to copy, communicate to the
public, adapt, distribute, transfer, sell, modify or publish any contents
of this document without the express prior written consent of System
Sensor.

Disclaimer

The contents of this document is provided on an “as is” basis. No
representation or warranty (either express or implied) is made as to the
completeness, accuracy or reliability of the contents of this document.
The manufacturer reserves the right to change designs or specifications
without obligation and without further notice. Except as otherwise
provided, all warranties, express or implied, including without
limitation any implied warranties of merchantability and fitness for a
particular purpose are expressly excluded.

General Warning

This product must only be installed, configured and used strictly in
accordance with the General Terms and Conditions, User Manual and
product documents available from System Sensor. All proper health
and safety precautions must be taken during the installation,
commissioning and maintenance of the product. The system should not
be connected to a power source until all the components have been
installed. Proper safety precautions must be taken during tests and
maintenance of the products when these are still connected to the power
source. Failure to do so or tampering with the electronics inside the
products can result in an electric shock causing injury or death and may

cause equipment damage. System Sensor is not responsible and cannot
be held accountable for any liability that may arise due to improper use
of the equipment and/or failure to take proper precautions.

Critical Product Security

Open Source Software

This product contains open source software provided by third parties. It
does not necessarily use all of the third party software components. Go
to

http://www.security.honeywell.com/opensource/

for a detailed list of

the third party software used and the associated open source license
agreement(s).

Firmware Updates

This device supports firmware upgrades via its USB port. When
performing a firmware update the new firmware update file should be
downloaded from the System Sensor website and saved to a USB
memory device that has had all of its content removed.

Approved firmware version: S05-0089-006.

Device and System Security

Before installing this product ensure that the two security seals on the
packaging are unbroken and the product has not been tampered with
since leaving the factory. Do not install this product if there are any
indications of tampering. If there are any signs of tampering the product
should be returned to the point of purchase.

It is the responsibility of the system owner to ensure that all system
components, i.e. devices, panels, wiring etc., are adequately protected to
avoid tampering of the system that could result in information
disclosure, spoofing, and integrity violation.

This device utilizes Secure Boot to validate the device’s software using
a hardware root of trust and cryptographic signatures. If the software

OSI-RIE-xx
Smoke Detection System

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Pittway Tecnologica S.r.l.,

Via Caboto 19/3,

34147 TRIESTE, Italy

1

E56-6965-000

Содержание OSI-RIE Series

Страница 1: ...ailable from System Sensor All proper health and safety precautions must be taken during the installation commissioning and maintenance of the product The system should not be connected to a power sou...

Страница 2: ...any provision outlined above is found to be invalid or unenforceable by a court of law such invalidity or unenforceability will not affect the remainder which will continue in full force and effect Al...

Страница 3: ...o section Humidity 0 to 95 RH Non condensing Mechanical Value Shipping Weight Complete unit 3 91 lbs 1 77kg Shipping Size 10 7 8 X 8 7 8 X 7 26 28 cm x 21 2 cm x17 78 cm Mounting Wall only without opt...

Страница 4: ...4 E56 6965 000 Dimensions Figure 3 1 Detector dimensions...

Страница 5: ...5 E56 6965 000 140 mm Figure 3 2 Reflector dimensions...

Страница 6: ...he conditions above can be addressed or minimized Some examples of applications for beam detectors might include aircraft hangars cold storage warehouses shipping warehouses enclosed parking facilitie...

Страница 7: ...sidewall may be used as a guide See Figure 3 3 The beam detector can be mounted with the transmitter receiver on one wall and the reflector on the opposite wall or both suspended from the ceiling or a...

Страница 8: ...uisance alarm or trouble conditions Initial selection of a proper mounting surface will eliminate false alarms and nuisance trouble signals Mount the detector on a stable mounting surface such as bric...

Страница 9: ...jects such as ductwork or windows should be a minimum 2 out of the center of the beam path of the beam In cases where reflective objects cannot be avoided the complete reflector blockage test can be u...

Страница 10: ...hen using one of the optional remote test stations Figure 3 16 shows the remote outputs for trouble and alarm Warning Disable the zone or system before applying power to the beam detector to prevent u...

Страница 11: ...to confirm that there are no obstructions or reflective objects within 15 38 1cm of the beam s path Insert the OSP 002 in the slot provided in the eyeball at 06 00 and move the eyeball The eyeball mo...

Страница 12: ...oing maintenance to prevent unwanted alarms Before testing the detector check for the presence of the flashing green OK LED at the receiver making sure not to disturb or block the beam If it does not...

Страница 13: ...nce Congratulations You have completed the final installation and alignment procedure Operation After A Power Failure The detector has the reflector location position set sensitivity and other commiss...

Страница 14: ...Station l Blinks till reset from FACP Trouble Drift Compensation Off 3 Quick Blinks Blink Long Term Drift Reference Out of 20 Range l Reduced IR Signal l Clean detector and reflector Trouble Beam Bloc...

Страница 15: ...uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that...

Страница 16: ...tion number send defective units postage prepaid to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Compa...

Отзывы: