INSTALLATION AND MAINTENANCE INSTRUCTIONS
Model LASS-WSS-NC
Addressable Wall Mount Sounder&Strobe
Xi'an System Sensor Electronics Ltd.
28 Tuanjie South Road
Xi'an Hi-tech Development Zone
710075, China
Tel: (+86) 029 85387800 Fax: (+86) 029 88332959
SPECIFICATION
Item
Parameter Description
Note
Operating Voltage
DC24V( DC15V~ DC32V)
Avg. Standby Current
<400µA
24VDC, No Communication, No sounding/flashing
Alarm Current
<11mA
High Volume, 24VDC
<8.5mA
Low Volume, 24VDC
Operating Temp
-25
℃
~+70
℃
Humidity 10~95%
R.H.
Non-condensing
Ingress Protection
IP33
IP35(With Water-proof box )
High Volume
90
±
4dB(A)
1m , High Volume, Tone 21 @24V
92
±
3dB(A)
1m , High Volume, Tone 13 @24V
91
±
5dB(A)
1m , High Volume, Tone 12 @24V
95
±
5dB(A)
1m , High Volume, Tone 19 @24V
Low Volume
86
±
3dB(A)
1m , Low Volume, Tone 21 @24V
86
±
4dB(A)
1m , Low Volume, Tone 13 @24V
81
±
3dB(A)
1m , Low Volume, Tone 12 @24V
84
±
6dB(A)
1m , Low Volume, Tone 19 @24V
Tone Type
4
See table 1: ‘Sound setting ’ for detailed tones
Flash Pattern
2
See table 2: ‘Flash Pattern’
Flash Intensity
>1cd
Coverage Volume
W-3-6/O-3-6
Height 47mm
Diameter 122mm
Weight
176
±
6g
Meet the following Standards requirements
:
EN54-3 & EN54-23
AS ISO 7240.3:2014 & AS ISO 7240.23:2014
Before installing and using the product, please read the system
wiring and installation manual thoroughly. If the products will
be installed in an existing operational system, inform
the operator
and local authority that the system will be temporarily out of
service, disconnect
power to the control panel before installing the
products.
NOTICE: This manual should be left with the owner/user of this
equipment.
GENERAL
LASS-WSS-NC is an intelligent addressable AV products
designed to alarm light/sound for emergency events, and be
able to communicate with control panel by intelligent protocol.
It is designed specifically for analogue addressable fire alarm
system and only can be connected to control panels with a
compatible proprietary analogue addressable communication
protocol. It is powered from the loop and can be controlled via
the communication protocol(s). The Wall Mount Version is
compatible with B501 mounting base. Up to 99 addresses are
available via two rotary selector switches. The sounders have
2 volume levels (high/low) and 4 tone sets. The alarm
light/sound can be tested on field.
INSTALLATION
It must be installed and wired with B501 mounting base.
1.
Verify the product type matches with product drawing.
2.
Set the address via two rotary selector switches. Please
refer to “Address setting”.
3.
Volume and tone setting are realized by 4 digit DIP witch.
On field testing can be tested via DIP switch.
4.
Plug the
Wall Mount Sounder& Strobe
into B501 mounting
base.
5.
Turn the
Wall Mount Sounder& Strobe
clockwise until it
drops into place.
6.
Continue turning the
Wall Mount Sounder& Strobe
clockwise
to lock it in place.
Figure 1
SETTING
Address setting
Rotary-decade switches are provided for setting the address
whose range is from 1 to 99. (Default address is 01).
Address is set by turning the switches.
Address is calculated as below formula: Address = TENS *10
+ ONES*1. For instance: Address 05 = 0*10 + 5*1.
I5
6
-59
25-
000
A5665
‐
006
B501
Mounting
Base
Wall Mount
Sounder&
Strobe