DNRE Duct Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Table of Contents 

Page

[1] Limitations of Duct Smoke Detectors   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .1
[2] General Description    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .1
[3] Contents of the Duct Smoke Detector Kit   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .1
[4] Detector Installation   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .1
[5] Sampling Tube Installation    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .2
[6] Measurement Tests   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .3
[7] Field Wiring   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .4
[8] Verification of Operation   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .4
[9] Dectector Cleaning Procedures    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .5
[10] Sensor Replacement    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .5
[11] Optional Accessories   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .5
Warranty 

   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .6

BEfORE INSTALLINg

Read the System Sensor Guide for 

Proper Use of Smoke Detectors in Duct Appli-

cations

 (A05-1004), which provides detailed information on detector spacing, 

placement, zoning, wiring, and special applications . Copies of this manual are 
available online at www .systemsensor .com . Reference must be made to local 
fire regulations . 

NOTICE: This manual shall be left with the owner/user of this equipment .
IMPORTANT: This detector must be tested and maintained regularly . The 
detector must be tested an maintained regularly following NFPA 72 require-
ments . According to NFPA, the detector should be visually inspected semian-
nually and functionally tested at least once a year .  This may need to be more 
frequent depending on the air quality of the duct supply air .

[1]LIMITATIONS Of DUCT SMOkE DETECTORS 

WARNING

DUCT DETECTORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA 
DETECTOR PROTECTION as a means of providing life safety . Nor are they a 
substitute for early warning in a building’s regular fire detection system .

This device will not operate without electrical power . Fire situations may 
cause an interruption of power . The system safeguards should be discussed 
with your local fire protection specialist .

This device will not sense smoke unless the ventilation system is operating 
and the cover is installed .

For this detector to function properly, it MUST be installed according to the 
instructions in this manual . Furthermore, the detector MUST be operated within 
ALL electrical and environmental specifications listed in this manual and the 
sensor head installation manual . Failure to comply with these requirements may 
prevent the detector from activating when smoke is present in the air duct .

[2]gENERAL DESCRIPTION

Smoke introduced into this air duct system will be distributed throughout the 
entire building . Smoke detectors designed for use in air duct systems are used 
to sense the presence of smoke in the duct . 

Model DNRE Air Duct Smoke Detector utilizes photoelectric technology for 
the detection of smoke . This detection method, when combined with an ef-
ficient housing design, samples air passing through the duct and allows detec-
tion of a developing hazardous condition . When sufficient smoke is sensed, 
an alarm signal is initiated at the fire control panel monitoring the detector, 
and appropriate action can be taken to shut off fans, blowers, change over air 
handling systems, etc . These actions can facilitate the management of toxic 
smoke and fire gases throughout the areas served by the duct system .

The DNRE incorporates a sensor cover tamper feature that provides a trou-
ble signal at the panel immediately if the cover is removed or improperly in-
stalled .  Proper installation of the sensor cover removes the trouble condition .

When programmed with the system control panel, two LEDs on each duct 
smoke detector light to provide local visible indication .  

The DNRE provides a remote alarm output for use with auxiliary devices, such 
as the RA400Z/RA100Z remote LED annunciator, as well as remote test capabil-
ity with the RTS451/RTS151 or RTS451KEY/RTS151KEY Remote Test Stations .

[2.1] DETECTOR fEATURE SET

– Utilizes plug-in head
– Sampling tubes install from front and rear
– Compatible with existing accessories
– Able to address detector per code switches on sensor head .

[3]CONTENTS Of ThE DUCT SMOkE DETECTOR kIT

1 .   Sensor/power side and covers (use appropriate sensor per the system 

control panel)

2 .  Three #10 sheet metal screws for mounting
3 .  One test magnet
4 .  Drilling template
5 .  One sampling tube end cap
6 .  One plastic exhaust tube
NOTE: A DST sampling tube must be ordered to complete the installation . It 
must be the correct length for the width of the duct where it will be installed . See 
Table 1 on page 3 to determine the inlet tube required for different duct widths . 

[4]DETECTOR INSTALLATION 
[4.1]VERIfy DUCT AIR fLOw DIRECTION AND VELOCITy

Model DNRE detectors are designed to be used in air handling systems hav-
ing air velocities of 1 .5 to 20 .3 m/sec per minute . Duct widths from 15 .3 to 
30 .5 cm can be accommodated . Be sure to check engineering specifications to 
ensure that the air velocity in the duct falls within these parameters . If neces-
sary, use a velocity meter (anemometer) to check the air velocity in the duct .

I56-3538-00

3R

SPECIfICATIONS 

Operating Temperature: 

–20° to 60° C

Storage Temperature: 

–30° to 60° C

Humidity: 

0% to 93% Relative Humidity Non-condensing

Air Velocity: 

1 .5 to 20 .3 m/sec .

Rectangular Footprint Dimensions: 

37 cm L × 12 .7 cm W × 6 .36 cm D

Square Footprint Dimensions: 

19 .7 cm L × 22 .9 cm W × 6 .35 cm D

Weight: 

0 .73 kg

Electrical (See applicable detector head installation manual for electrical specifications . Use the Base/Sensor Cross Reference chart at http:\\www .systemsensor .com 
to determine applicable sensor head .)

ACCESSORY CURRENT LOADS AT 24 VDC

DEVICE

STANDBY

ALARM

RA400Z/RA100Z

0mA

12mA Max.

RTS451/RTS151

0mA

12mA Max.

RTS451KEY/RTS151KEY

12mA

12mA Max.

6500RTS-KEY

12mA

12mA Max.

Pittway Tecnologica Srl,

Via Caboto 19/3, 34147 Trieste, Italy

www .systemsensoreurope .com

Содержание Innovair Flex DNRE

Страница 1: ...ondition When sufficient smoke is sensed an alarm signal is initiated at the fire control panel monitoring the detector and appropriate action can be taken to shut off fans blowers change over air handling systems etc These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system The DNRE incorporates a sensor cover tamper feature that prov...

Страница 2: ...inch diameter holes using a 4 mm drill at target B centers 4 3 2 For square top over bottom mounting configuration Center punch at 4 target centers 2 A for sampling tubes and 2 C for the square configuration mounting tabs as shown on mounting template Drill pilot holes at target A centers and cut two 3 5 cm diameter holes using a 3 5 cm hole saw or punch Drill 4 mm diameter holes using a 4mm drill...

Страница 3: ...from the chamber and reset the duct smoke detector at the panel Use duct tape to seal the aerosol smoke entry hole Remember to replace the cover after the test or the detector will not function properly CAUTION Canned aerosol simulated smoke canned smoke agent formulas will vary by manufacturer Misuse or overuse to these products may have long term adverse effects on the smoke detector Consult the...

Страница 4: ...exhaust tube model ETX is available as an accessory in cases where the molded exhaust tube does not extend at least 5 cm into the duct 5 2 Sampling Tube Installation 1 For tubes shorter than the width of the duct slide the sampling tube with installed end cap into the housing connection that meets the air flow first Position the tube so that the arrow points into the airflow as shown in Figure 3 S...