background image

% DIRTY

0000

If the device is a photo-duct detector, the following screen will appear:

PHO-DUCT

DETECTOR

If the down arrow is pressed again, a screen similar to this one will appear:

S1:XXX

S2:XXX

This screen shows the levels of sensitivity for the selected device. Pressing the 
down arrow again will show how dirty the detector is. This is indicated as the 
percentage of drift compensation limit used. Please refer to the control panel 
installation manual for the percentage that requires cleaning. 

If the device is a photo detector, the following screen will appear:

PhotoDCT

Detector

If the down arrow is pressed again, a screen similar to this one will show up if 
the device is configured to Acclimate.

AHIS: 0.5 

ALOS: 4.0

This screen shows the Acclimate sensitivity range of the photo detector. The 
AHIS is the upper limit of the sensitivity range in percent per foot. The ALOS 
indicates the lower limit of the sensitivity range in percent per foot. Detector 
sensitivity cannot be changed using the EA-CT. Please refer to the control 
panel installation manual to change the levels of sensitivity on the detector. 

If the down arrow is pressed again  a screen similar to this one will appear:

SENS 

LEVEL: 2.4

If the device is not configured to Acclimate the following screen similar to this 
one will appear:

S1:XXX

S2:XXX

This shows the sensitivity level corresponding to the sensitivity broadcasts. 
Pressing the down arrow again will show the how dirty the detector is. This 
is indicated as the percentage of drift compensation limit used. Please refer to 
the control panel installation manual for the percentage that requires cleaning.

If the device is an Ion detector, the following screen will appear:

ION     SE 

DETECTOR

If the down arrow is pressed again, a screen simliar to this one will show up if 
the device is configured to Acclimate:

AHIS.X.X%

  XXMIC

If the down arrow is pressed again, a screen simliar to this one will show up:

ALOS X.X%

  XXMIC

If the down arrow is pressed again, a screen similar to this one will appear:

SENS X.X%

  XXMIC

If the device is not configured to Acclimate a screen similar to this one will appear:

S1: X.X%

  XXMIC

If the down arrow is pressed again, a screen similar to this one will appear:

S2: X.X%

  XXMIC

This shows the sensitivity level corresponding to the sensitivity broadcasts. 
Pressing the down arrow again will show how dirty the detector is. This is 
indicated as the percentage of drift compensation limit used. Please refer to 
the control panel installation manual for the percentage that requires cleaning.

If the device is a control module, the following screen will appear:

CONTROL 

MODULE

If the device is a relay module, the following screen will appear:

RELAY 

MODULE

If the device is a monitor module, the following screen will appear:

MONITOR 

MODULE

If the device is mini module, the following screen will appear:

MINI 

MODULE

If the device is a pull station, the following screen will appear:

PULL 

STATION

If the device is conventional zone module, the following screen will appear: 

CONV ZON

MODULE

If the device is dual monitor module, the following screen will appear:

DUAL MON

MODULE

When the down arrow is pressed again on all ECLIPSE devices the screen will 
show the date when each device was last serviced (if the service data was 
set during the last service). If the Menu Settings are set to US format the date 
format will be MM/DD/YY. If the settings are Non-US setting the date will be 
displayed as DD/MM/YY. 

SERVICED

07/16/12

When the down arrow is pressed again on all devices, the display will show the 
date the device was manufactured in weeks of the year followed by the year.

MANUF.:

WK: 02,11

4. WRITE SERVICE

This setting allows a service technician to record when the selected Eclipse de-
vice has been serviced. When this choice is made, the EA-CT will request the 
user to point to the selected device, and if the communication is successful,  a 
screen similar to the following is displayed:

SERVICED:

10/10/95

NOTE:

 The service date is automatically entered as the current date and can-

not be changed to a different day. 

5. TEST MODES

5.1 TEST ALARM

This option will cause a device to self-test. Point to the selected device that re-
quires testing and press enter. When the communication is complete, a screen 
similar to this will be displayed:

OK ALARM TEST SET

Optionally “

SE

” will appear if smoldering is enabled

Reporting the Acclimate Hi sensitivity

Reporting the Acclimate Low sensitivity

Showing the current detector’s sensitivity

  

I56-2245-006 

 

 06-10

Содержание EA-CT

Страница 1: ... device that has been se lected it may be deselected and another device chosen instead Loop Loop and address are the two components of a device s identifier in an Eclipse system With Eclipse multiple loops may reside on the same pair of wires Loops can be numbered 1 to 254 Master Key If a user misplaces their PIN number the EA CT can generate a code or master key that will allow technical support ...

Страница 2: ...ey on this op tion and after the set new branch screen is displayed the following screen will come up BRANCH XXX Enter the branch number that is desired Point the EA CT at the device that is to receive the branch marker Press enter and after a moment the EA CT will display BRANCH NUM set To display the new branch number press ESC twice BRANCH IS XXX NOTE If the selected device does not contain iso...

Страница 3: ...n arrow is pressed again a screen similar to this one will appear S2 X X XXMIC This shows the sensitivity level corresponding to the sensitivity broadcasts Pressing the down arrow again will show how dirty the detector is This is indicated as the percentage of drift compensation limit used Please refer to the control panel installation manual for the percentage that requires cleaning If the device...

Страница 4: ...ollowing screen will be displayed SET MENU STYLES US EU Use the arrow keys to select the requested choice and press the enter key The date codes will automatically be displayed in the requested format THREE YEAR LIMITED WARRANTY System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manu...