DH400ACDC Air Duct Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read the System Sensor 

Guide for Proper

Use of Smoke Detectors in Duct Applications 

(I56-473)

,

which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Copies
of this manual are available from System Sensor. NFPA
Standards 72 and 90A should also be referenced for de-
tailed information.

NOTICE:

 This manual should be left with the owner/user

of this equipment.

IMPORTANT: 

This detector must be tested and maintained

regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.

Table of Contents

Page

[1]

General Description

1

[2]

Exploded View of Duct Detector Components

2

[3]

Contents of the Duct Detector Kit

2

[4]

Limitations of Duct Detectors

2

[5]

Installation Sequence

2

[6]

Duct Detector Maintenance and Test Procedures

8

[7]

Detector Cleaning Procedures

10

[8]

Specifications

12

Warranty

13

Detector Test log

16

List of Tables and Figures

Page

Fig. 1: Duct Detector Exploded View

2

Fig. 2: Installation of Sampling Tube Gaskets

3

Fig. 3: Mounting Location of Speed Nuts

3

Table 1: Inlet Sampling Tube Selection

3

Fig. 4: Inlet Sampling Tube

4

Fig. 5: Sampling Tube Mounting Configurations

4

Fig. 6: Wiring Diagram

6

Fig. 7: Wiring Diagram – No Control Panel

7

Fig. 8: Wiring Diagram – Accessories

8

Fig. 9: Sampling Tube Filter Installation

8

Fig. 10: Testing Detector Alarm

9

Fig. 11: Detector Head Removal

9

Fig. 12: RTS451/RTS451KEY Test Coil Installation

10

Fig. 13: Photo Head Exploded View

11

Fig. 14: Ion Head Exploded View

11

[1] General Description

An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense
the presence of smoke in the duct.

Model DH400ACDC Air Duct Smoke Detectors are supplied
with model 1451DH ionization detector heads or model
2451 photoelectronic detector heads. These two smoke de-
tection methods are combined with an efficient housing de-
sign that samples air passing through a duct and allows
detection of a developing hazardous condition. When suffi-
cient smoke is sensed, an alarm signal is initiated at the fire
control panel monitoring the detector, and appropriate ac-
tion can be taken to shut off fans and blowers, change over
air handling systems, etc. These actions can facilitate the
management of toxic smoke and fire gases throughout the
areas served by the duct system.

DH400ACDC detectors are designed to operate from 24
VDC, 24 VAC, 120 VAC, or 240 VAC. Alarm and supervisory
relay contacts are available for control panel interface
(alarm initiation), HVAC control, and other auxiliary func-
tions. These detectors are not designed for 2-wire applica-
tion.

For testing, the alarm can be enabled by a magnet activated
test switch, by insertion of a calibrated test card into the
sensing chamber (photoelectronic version only), or by the
optional remote test station. The duct smoke detectors
latch into alarm state when alarm occurs. LEDs on each de-
tector illuminate to provide local alarm indication, and op-
tional accessories offer a variety of annunciation
capabilities.

The detector can be reset by a momentary power interrup-
tion, by the magnet activated reset switch, or by the op-
tional remote test station.

Содержание DH400ACDC

Страница 1: ... Photo Head Exploded View 11 Fig 14 Ion Head Exploded View 11 1 General Description An HVAC system supplies conditioned air to virtually every area of a building Smoke introduced into this air duct sys tem will be distributed to the entire building Smoke detec tors designed for use in air duct systems are used to sense the presence of smoke in the duct Model DH400ACDC Air Duct Smoke Detectors are ...

Страница 2: ...m safeguards should be discussed with your local fire protection specialist WARNING This device does not sense smoke unless the ventilation system is operating CAUTION For this detector to function properly it MUST be installed according to the instructions in this manual Furthermore the detector MUST be protected from the elements and op erated within ALL electrical and environmental specifica ti...

Страница 3: ... TUBE EXTENSION BUSHING DUCT DETECTOR HOUSING O RINGS MOUNTING SCREWS INLET SAMPLING TUBE BUSHING A78 2045 00 Figure 3 Speed nut mounting location HOLE B HOLE A DUCT WALL SPEED NUT 78 2046 00 5 4 Install The Inlet The inlet tube shown in Figure 4 is identified by a series of air inlet holes on the tube This tube must be purchased separately Order the correct length as specified in Table 1 for widt...

Страница 4: ...tector inlet sampling tube INLET TUBE END PLUG AIR HOLES ARROWS MUST FACE INTO AIR FLOW AIR FLOW DIRECTION FLANGE A78 2047 00 AIR FLOW DIRECTION DUCT DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DUCT DETECTOR HOUSING INLET TUBE EXHAUST TUBE AIR FLOW DIRECTION INLET TUBE EXHAUST TUBE INLET TUBE EXHAUST TUBE DUCT DETECTOR HOUSING AIR FLOW DIRECTION EXHAUST TUBE I...

Страница 5: ...l and add the appropri ate number of holes so that the total number of holes ex posed to the air flow in the duct is 10 to 12 Space the additional holes as evenly as possible over the length of the tube 5 5 Field Wiring Wiring Installation Guidelines All wiring must be installed in compliance with the Na tional Electrical Code and the local codes having jurisdic tion Proper wire gauges should be u...

Страница 6: ...WN OPEN IN STANDBY CONTACTS CLOSE IN ALARM 8 9 ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY CONTACTS CLOSE IN ALARM ALARM INITIATION LOOP UL LISTED CONTROL PANEL FIRST DETECTOR IN THE LOOP DH400ACDC LAST DETECTOR IN THE LOOP DH400ACDC EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPL...

Страница 7: ...ICES REFER TO MANUFACTURER S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER TROUBLE CONTACT RATING 0 3A 32 VAC DC POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR ALARM AUXILIARY CONTACT RATINGS 10A 30 VDC 10A 250 VAC 500mA MINIMUM 24 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS ALARM INITIATI...

Страница 8: ...AY BE USED SUCH THAT THE GIVEN CURRENT LOADS TOTAL RESET TEST NOTE WHEN INITIATING AN ALARM THE RTS451 RTS451KEY REQUIRES 95mA MAXIMUM IN PRE ALARM AND 103mA MAXIMUM IN ALARM NOMINAL STANDBY CURRENT IS 0mA ALARM CURRENT IS 10mA MAXIMUM WHEN TEST MAGNET IS REMOVED 100mA OR LESS IN THE STANDBY STATE 150mA OR LESS IN THE ALARM STATE A78 2354 00 5 7 Perform Detector Check 1 Perform the STANDBY AND TRO...

Страница 9: ...1 Detector head removal TEST LOCATOR TEST MAGNET PAINTED SIDE TOWARD HOUSING DUCT HOUSING DETECTOR HEAD RESET LOCATOR TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TWIST CLOCKWISE TO INSTALL DETECTOR HEAD A78 2138 00 A78 2139 00 Trouble If the detector LEDs do not blink or if the APA451 Power LED is not illuminated the detec tor lacks power check wiring panel or power supply the head is missing in...

Страница 10: ... can be turned counterclock wise DETECTOR HEAD TEST COIL Figure 12 RTS451 RTS451KEY test coil installation A78 1994 02 4 Carefully reinsert the detector head into the duct hous ing and wait 50 seconds for power up Do not hold the swirl chamber to twist the detector head 5 Insert the NO ALARM end of the test card into the test slot see Figure 13 and slide it counterclockwise until it stops The dete...

Страница 11: ...screens RS14 are available 4 Brush or vacuum the inside of the cover The cover may then be blown out with clean compressed air 5 Vacuum the sensing chamber before using clean com pressed air to loosen and blow out any remaining debris 6 Press the screen back into the cover 7 Replace the detector cover onto the sensing chamber Rotate it clockwise to lock it into place REMOVABLE HEAD COVER CLEANABLE...

Страница 12: ... sems plates accept wire sizes of 14 gauge or smaller The screws can withstand 10 in lbs of tightening torque without damage Accessories MOD400R Sensitivity Test Module RA400Z Remote Annunciator RTS451 RTS451KEY Remote Test Station test reset switch with alarm LED PA400 Piezo Sounder APA451 Annunciator with piezo alarm power LEDs CRT400 Cover Removal Tool Ion only F36 05 00 Replacement Air Filter ...

Страница 13: ...MINAL STANDBY CURRENT IS 0mA ALARM CURRENT IS 10 mA MAXIMUM WHEN TEST MAGNET IS REMOVED Three Year Limited Warranty System Sensor warrants its enclosed air duct smoke detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture System Sensor makes no other express warranty for this air duct smoke detector No agent r...

Страница 14: ...NOTES D400 13 00 14 I56 555 08 ...

Страница 15: ...NOTES D400 13 00 15 I56 555 08 ...

Страница 16: ..._______________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ____...

Отзывы: