Install the inlet tube as follows:

1. Drill a 3/4-inch hole in the duct directly opposite the

hole already drilled for the inlet tube.

2. Slide the inlet tube with the flange into the centermost

housing bushing. Position the tube so that the arrows
point into the air flow. Secure the tube flange to the
housing bushing with two #6 self-tapping screws.

3. From inside the duct, couple the other section of the in-

let tube to the section already installed using the 1/2-
inch conduit fitting supplied. Make sure that the holes
on both of the air inlet tubes are lined up and facing into
the air flow.

4. Trim the end of the tube protruding through the duct so

that 1 to 2 inches of the tube extend outside the duct.
Plug this end with the end plug and tape closed any
holes in the protruding section of the tube. Be sure to
seal the duct when the tube protrudes.

NOTE:

An alternate method to using the ST-10 is to use
two ST-5 inlet tubes. Remove the flange from one
of the tubes and install as described above. After
the installation, use electrical tape to close off
some of the sampling holes so that there are a total
of 10 to 12 holes spaced as evenly as possible
across the width of the duct.

NOTE:

Air currents inside the duct may cause excessive
vibration, especially when the longer sampling
tubes are used. In these cases a 3 inch floor flange
(available at most plumbing supply stores) may be
used to fasten the sampling tube to the other side
of the duct. When using the flange/connector
mounting technique, drill a 1 inch to 1-1/4 inch
hole where the flange will be used.

[5.4.3] Modifications of Inlet Sampling Tubes

There may be applications where duct widths are not what
is specified for the installation. In such cases, it is permis-
sible to modify an inlet sampling tube that is longer than
necessary to span the duct width.

Use a 0.193-inch diameter (#11) drill and add the appropri-
ate number of holes so that the total number of holes ex-
posed to the air flow in the duct is 10 to 12. Space the
additional holes as evenly as possible over the length of the
tube.

[5.5] Field Wiring

Wiring Installation Guidelines

All wiring must be installed in compliance with the Na-
tional Electrical Code and the local codes having jurisdic-
tion. Proper wire gauges should be used. The conductors
used to connect smoke detectors to control panels and ac-
cessory devices should be color-coded to prevent wiring
mistakes. Improper connections can prevent a system from
responding properly in the event of a fire.

For signal wiring, (the wiring between interconnected de-
tectors or from detectors to auxiliary devices), it is usually
recommended that single conductor wire be no smaller
than 18 gauge. The duct detector terminals accommodate
wire sizes up to 14 gauge. The last foot of conduit should
be flexible steel conduit (available in electrical supply
houses), which facilitates easier installation and puts less
strain on the conduit holes in the housing. Solid conduit
connections may be used if desired.

Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel manufacturer’s specifications for the total
loop resistance allowed for the particular model control
panel being used before wiring the detector loop.

Wiring Instructions

The DH400 detectors are designed for easy wiring. The
housing provides a terminal strip with clamping plates.
Wiring connections are made by stripping about 3/8-inch
of insulation from the end of the wire, sliding the bare end
under the plate, and tightening the clamping plate screw.

DH400 detectors are designed to operate with 12 or 24 VDC
UL listed 2-wire compatible control panels. Alarm current
must be limited by the control panel to 100mA or less. An
example of a UL listed compatible control panel is the Fire-
Lite model Sensiscan 1000 using zone card ANC-2 and
compatibility identification “A”. Install per installation in-
struction S1000/801. A maximum of 20 detectors may be
installed per zone.

D400-14-00

5

I56-554-05

Содержание DH400

Страница 1: ... Fig 12 Photo Head Exploded View 11 Fig 13 Ion Head Exploded View 11 1 General Description An HVAC system supplies conditioned air to virtually every area of a building Smoke introduced into this air duct sys tem will be distributed to the entire building Smoke detec tors designed for use in air duct systems are used to sense the presence of smoke in the duct Model DH400 Air Duct Smoke Detectors a...

Страница 2: ...building s regular fire detection system System Sensor supports this position and strongly recom mends that the user read NFPA Standards 90A 72 and 101 The DH400 Air Duct Smoke Detectors are listed per UL 268A WARNING This device will not operate without electrical power Frequently fire situations may cause an interruption of power The system safeguards should be discussed with your local fire pro...

Страница 3: ...045 00 Figure 3 Speed nut mounting location HOLE B HOLE A DUCT WALL SPEED NUT A78 2046 00 5 4 Install The Inlet The inlet tube shown in Figure 4 is identified by a series of air inlet holes on the tube This tube must be purchased separately Order the correct length as specified in Table 1 for width of the duct where it will be installed The exhaust tube is molded onto the base of the duct housing ...

Страница 4: ...IR HOLES ARROWS MUST FACE INTO AIR FLOW AIR FLOW DIRECTION FLANGE Figure 4 Air duct detector inlet sampling tube A78 2047 00 Figure 5 Tube mounting configurations with varying air flow direction A78 1812 01 AIR FLOW DIRECTION DUCT DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DUCT DETECTOR HOUSING INLET TUBE EXHAUST TUBE AIR FLOW DIRECTION INLET TUBE EXHAUST TUB...

Страница 5: ... that the total number of holes ex posed to the air flow in the duct is 10 to 12 Space the additional holes as evenly as possible over the length of the tube 5 5 Field Wiring Wiring Installation Guidelines All wiring must be installed in compliance with the Na tional Electrical Code and the local codes having jurisdic tion Proper wire gauges should be used The conductors used to connect smoke dete...

Страница 6: ...0Z OPTIONAL REMOTE ALARM LED 5 mA MAX 2 8 VDC NOM IN ALARM E O L R STYLE D OPTIONAL WIRING UL LISTED COMPATIBLE 2 WIRE CONTROL PANEL ALARM INITIATION LOOP EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections A78 2350 00 Figure 6 System wiring diagram for 2 wire duct detectors detecto...

Страница 7: ...ET TEST SWITCH ALARM LED RED 1 2 4 5 3 4 6 7 8 2 8 VDC IN ALARM 24 VDC AUX POWER SUPPLIED BY USER 100mA SUPPLY MAGNET TEST SWITCH ALARM LED RED 1 2 4 5 3 4 6 7 2 8 VDC IN ALARM 24 VAC 10 15 FULL WAVE RECTIFIED UNFILTERED POWER MAY BE USED RTS451 RTS451KEY OPTIONAL REMOTE TEST STATION DH400 DUCT DETECTOR METHOD 2 AUX POWER LOCATED AT TEST STATION Figure 7 Wiring diagram for RTS451 RTS451KEY Remote ...

Страница 8: ...ews that are fixed in the housing cover Be certain filters are installed as specified in Section 5 6 Make sure that the cover fits into the base groove and that all gaskets are in their proper positions Tighten the four cover screws to 10 in lbs 6 Duct Detector Maintenance And Test Procedures Test and maintain duct detectors as recommended in NFPA 72 The tests contained in this manual were devised...

Страница 9: ... M02 04 00 Magnet Test 1 Place the painted surface of the magnet into the TEST locator molded into the side of the housing Figure 9 2 The red alarm LEDs on the detector should latch on as Figure 9 Testing detector alarm Figure 10 Detector head removal TEST LOCATOR TEST MAGNET PAINTED SIDE TOWARD HOUSING DUCT HOUSING DETECTOR HEAD TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TWIST CLOCKWISE TO INS...

Страница 10: ...wise until it stops The LEDs should latch on within 20 seconds Remove card and reset detector at system control panel DETECTOR HEAD TEST COIL Figure 11 RTS451 RTS451KEY test coil installation A78 1994 02 7 Put the cover back by gently rotating it clockwise until it locks in place Secure the duct housing cover using the 4 cover screws 7 Detector Cleaning Procedures Notify the proper authorities tha...

Страница 11: ...m pressed air to loosen and blow out any remaining debris 6 Press screen back into cover 7 Replace detector cover onto sensing chamber Turn clockwise to lock into place 7 4 Reinstallation 1 Reinstall detector in housing 2 Restore system power 3 Perform Detector Check Section 5 7 of this manual 4 Notify the proper authorities that testing has been com pleted and the smoke detector system is operati...

Страница 12: ...ws will withstand 10 in lbs of tightening torque without damage Accessories M02 04 00 Replacement Test Magnet RA400Z Remote Annunciator alarm LED RTS451 RTS451KEY Remote Test Station test switch with alarm and power LEDs CRT400 Cover Removal Tool Ion only F36 05 00 Replacement Air Filter two per package MOD400R Sensitivity Test Module P48 21 00 Replacement End Plug for inlet sampling tube R59 18 0...

Страница 13: ... limited to the repair or re placement of any part of the air duct smoke detector which is found to be defective in materials or workmanship under normal use and service dur ing the three year period commencing with the date of manufacture After phoning System Sensor s toll free number 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid to System Sensor Repa...

Страница 14: ...NOTES D400 14 00 14 I56 554 05 ...

Страница 15: ...D400 14 00 15 I56 554 05 NOTES ...

Страница 16: ...________ _____________________________ ________ ____________ ________ _______________ _____________________________ ________ ____________ ________ _______________ _____________________________ ________ ____________ ________ _______________ _____________________________ ________ ____________ ________ _______________ _____________________________ ________ ____________ ________ _______________ ______...

Отзывы: