System Sensor CH1224 Скачать руководство пользователя страница 1

D900-00-00                                                                                 1                                                                             I56-0003-004R

Electronic Chime/Sounder

For use with the following models:

Chime/Sounder: 12/24 volt: CH12/24

Add suffix “W” for white models.
The Products to which this manual applies may be covered by one or more of the following U. S. Patent Numbers: 5,914,665; 6,133,843

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

General Description

The  SpectrAlert  series  notification  appliances  are  designed  to  meet  the 
requirements of most agencies governing these devices, including: NFPA, 
The  National  Fire  Alarm  Code,  UL,  CSFM,  MEA.  Also,  check  with  your 
local Authority Having Jurisdiction for other codes or standards that may 
apply.

These  Chime/Sounders  are  non-synchronous  and  are  not  MDL  compat-
ible.

The Chime/Sounder series can be installed in systems using 12- or 24-volt 
panels having DC or full-wave rectified (FWR) power supplies.

NOTICE:

  This  manual  shall  be  left  with  the  owner/user  of  this  equip-

ment.

Fire Alarm System Considerations

Temporal and Non-Temporal Coded Signals:
The  American  National  Standards  Institute  and  the  National  Fire  Alarm 
Code  require  that  all  horns  used  for  building  evacuation  installed  after 
July  1,  1996,  must  produce  Temporal  Coded  Signals.  Signals  other  than 
those used for evacuation purposes do not have to produce the Temporal 
Coded Signal.

Power Supply Considerations

Panels  typically  supply  DC  filtered  voltage  or  FWR  (full-wave  rectified) 
voltage. The system design engineer must calculate the number of units 
used in a zone based on the type of panel supply. Be certain the sum of 
all the device currents does not exceed the current capability of the panel. 
Calculations are based on using the device current found in the subsequent 
charts and must be the current specified for the type of panel power sup-
ply used.

NOTE:   The  SpectrAlert  Electronic  Chime/Sounder  must  be  powered 

from a non-coded power supply. This appliance is not intended 
for use with a coded power supply.

Specifications

Voltages:                                   Regulated 12 DC/FWR and Regulated 24 DC/FWR
Operating Voltage Limits:           8–17.5 and 16–33
Maximum Operating Current
      At 12VDC:                          31 mA 
      At 24VDC:                          61 mA 
Operating Temperature:             32˚F to 120˚F (0˚C to 49˚C)
Sound Output:                          Sound  output  levels  are  established  at  Underwriters  Laboratories  in  their  reverberant  room.  Always  use  the  sound 

output specified as UL Reverberant Room when comparing products.

Listings:                                    UL 464; Private Mode

Wire Sizes

The designer must be sure that the last device on the circuit has sufficient 
voltage to operate the device within its rated voltage. When calculating 
the voltage available to the last device, it is necessary to consider the volt-
age drop due to the resistance of the wire. The thicker the wire, the less 
the voltage drop. Generally, for purposes of determining the wire size nec-
essary for the system, it is best to consider all of the devices as “lumped” 
on the end of the supply circuit (simulates “worst case”).

Typical wire size resistance:
18 AWG solid: 

Approximately 8 ohms/1,000 ft.

16 AWG solid: 

Approximately 5 ohms/1,000 ft. 

14 AWG solid: 

Approximately 3 ohms/1,000 ft.

12 AWG solid: 

Approximately 2 ohms/1,000 ft.

Example: Assume you have 10 devices on a zone and each requires 50 mA 
average and 2000 Ft. of 14 AWG wiring (total length=oureturn). 
The voltage at the end of the loop is 0.050 amps per device 

×

 10 devices 

×

 3 ohms/1,000 ft. 

×

 2000 ft =3 volts drop.

Note: If Class A wiring is installed, the wire length may be up to 4 times 
the single wire length in this calculation.

The same number of devices using 12 AWG wire will produce only 2 volts 
drop.  The  same  devices  using  18  AWG  wire  will  produce  8  volts  drop. 
Consult your panel manufacturer’s specifications, as well as SpectrAlert’s 
operating voltage range to determine acceptable voltage drop.

Chime Selection

Chimes are factory set for high volume, 1000Hz, 1 second chime. Tones 
may  be  selected  by  making  the  appropriate  settings  on  the  DIP  Switch 
located on the printed circuit board. The settings required for the available 
tone options are as follows:

Отзывы: