General Description

The  BEAMHKR  allows  the  reflector  of  the  System  Sensor  reflected  beam 
smoke detectors to operate in environments prone to the formation of con-
densation.

1

  Condensation  forming  on  the  reflector  may  result  in  trouble  or 

false  alarm  conditions.  BEAMHKR  will  lessen  the  likelihood  of  condensa-
tion  by  maintaining  the  reflector  at  a  temperature  that  is  slightly  higher 
than  the  surrounding  air.  The  kit  requires  a  24V  power  supply.  When  used 
with  the  long-range  reflector  kit  (BEAMLRK),  it  is  necessary  to  purchase 
and install four BEAMHKR kits.

The kit includes the following parts:
Qty. 

Description

 1 

Reflector Heater

Mounting and Wiring Instructions

1.  Insure that the back of the reflector(s) is clean and free of debris.

2.  See  Figure  1  below  (front  view)  for  recommended  mounting  orienta-

tion. See steps 3 and 4 for additional information.

Electrical Specifications

Voltage:  

15 to 32 Volts

Current:  

450mA max at 32 V

 

(per reflector)

Power Consumption (per reflector):  
 

Nominal: 

7.7 W at 24 V

 

Maximum: 

15 W at 32 V 

3.  Peel  off  the  protective  backing  from  the  back  of  the  heater.  This 

exposes the Pressure Sensitive Adhesive.

4.   Observing  proper  orientation  (see  Figure  2),  attach  the  heater  to  the 

back  of  the  reflector  as  shown.  Insure  that  the  four  holes  in  the  heater 
are  aligned  with  the  four  small  holes  on  the  back  of  the  reflector.  In 
addition,  insure  that  the  heater  tab  is  on  the  correct  side  of  the  reflec-
tor,  as  shown  in  Figure  1.  Repeat  for  remaining  three  reflectors  if  using 
BEAMLRK.

Single

Reflector

Heater

Tab

24 V +–

24 V +–

Used in conjunction

with BEAMLRK

Figure 1

Figure 2

C0764-00

C0763-00

5.  Mount  the  reflector(s).  Refer  to  the  installation  manual  provided  with 

the  beam  smoke  detector  for  instructions.  For  installations  in  conjunc-
tion  with  BEAMLRK,  refer  to  BEAMLRK  installation  manual  for  proper 
mounting practices and considerations.

6.  Attach  heater  wires  to  the  power  supply.  For  BEAMLRK,  the  four  indi-

vidual heaters are wired in a parallel. See Figure 1.

NOTES:
1.    The  heater  is  intended  for  the  prevention  of  condensation  only.  It  is 

not  intended  to  increase  or  reduce  the  specified  operating  temperature 
range of the beam smoke detector.