Specifications
Base Diameter:
6.2 inches (15.7 cm)
Base Height:
1.1 inches (2.9cm)
Weight:
0.6 lb. (260 g)
Mounting:
4-inch square box without plaster ring. Minimum depth–1.5 inches
4-inch octagon box. Minimum depth–1.5 inches
Operating Temperature Range:
0
°
to 49
°
C (32
°
to 120
°
F)
Operating Humidity Range:
10% to 93% Relative Humidity
Electrical Ratings – includes base and detector
System Voltage:
24 VAC/DC, 60 Hz
Relay Contact Ratings
Resistive or Inductive (60% power factor) load
Form A:
2.0A @ 30VAC/DC
Form C:
2.0A @ 30VAC/DC
0.6A @ 110VDC
1.0A @ 125VAC
(If used, the RA400 Remote Annunciator and RTC operates within the specified detec-
tor system voltage.)
Start-up Time:
36.0 Seconds maximum
(After 60 second reset)
Before Installing
Please thoroughly read System Sensor’s manual I56-407,
Guide for Proper Use of System Smoke Detectors
. This
manual provides detailed information on detector spacing,
placement, zoning, wiring, and special applications, and is
available at no charge from System Sensor.
NOTICE:
This manual should be left with the owner/user
of this equipment.
IMPORTANT:
The detector used with this base must be
tested and maintained regularly following NFPA 72 re-
quirements. The detector used with this base should be
cleaned at least once a year.
General Description
The B404BT detector base is designed for use with Sys-
tem Sensor model 2451 and 2451TH photoelectronic and
1451 ionization detector heads. The capability of plug-
ging these detectors into a variety of special bases
makes them more versatile than equivalent direct-wired
models. Refer to the System Sensor catalog for other
available plug-in bases. The B404BT base is intended for
use in 4-wire systems with terminals provided for re-
mote annunicator and relay connections.
Power
Wire leads are provided for 24 VAC/DC power operation.