IP Addressing
Scalibur’s default IP address of the primary IP interface (
eth0
) is
192.168.1.1
, the
subnet mask
255.255.255.0
. The secondary IP interface (
eth1
) is deactivated by
default. There are several ways to configure the IP settings:
SCA System Shell (see 4.1.1)
Commissioning website via
Settings/Network
(see 4.1.2)
Workbench via Platform connection with the Niagara daemon under
TCP/IP
Configuration
4.2.2
Time and Time Zone
The internal time is derived from a buffered RTC. At delivery the buffer capacitor is
usually discharged and the time at the first start of the Scalibur is set to midnight
2000-01-01. Time and time zone (default Central European Time CET or Central
European Summer Time CEST) can be configured in several ways:
SCA System Shell (see 4.1.1)
Commissioning website via
Settings
Date/Time
Workbench via Platform connection with the Niagara daemon under
Platform Administration
Change Date/Time
4.2.3
Hardware Data Point Test
Usually, the electrical connection and the software integration of control stations are
done by different persons and at different times. Ideally, the electrical installation
(mounting and cabling) should be finished with a data point test and its according
documentation. This is supported by the commissioning webserver, which clearly
visualizes all input and output signals of the IO terminals. If required, output
channels and also their configuration, like measuring ranges, can be manually
overridden. Thus, a data point test doesn’t need any application software. By leaving
the commissioning page (either manually or by timeout), all overrides are reverted.