User Manual of SY6000-Z series Maintenance
Chapter 7 Maintenance
7.1 Daily inspection
z
Hearing and touching the housing, check if there are abnormal heating,
noise and vibration from the cabinet and motor.
z
Check if ambient temperature and humidity exceeds the manual
provision by using thermometer and hygrometer.
z
Load current is in the range of rated value or not.
z
Cooling fan runs normally or not.
7.2 Regular maintenance
Start to check after no displaying of the monitor and turning off of the
main circuit power indicator.
Inspection contents are as shown in Table 7-1.
Table 7-1 Regular inspection contents
Inspection items
Inspection contents
Abnormal countermeasure
Main circuit terminal,
screw of control
circuit terminal
Loosening of screws
or not
Tighten with a screwdriver
Heat sink
Dust or not
User4~6kg/cm2 pressure
dry compressed air to blow
off
PCB Dust
or
not
User4~6kg/cm2 pressure dry
compressed air to blow off
Cooling fan
Abnormal noise,
abnormal vibration,
or total running time
up to 20,000 hours.
Replace cooling fan
Power components
Dust or not
User4~6kg/cm2 pressure
dry compressed air to blow
off
Aluminum capacitor
Discoloring,
off-favor, bubbling,
or not
Replace aluminum capacitor