Section II
General Product Information
006-0006205
UPS-1500 Series
Rev ZC
10 of 60
05/28/2019
Part Numbering Scheme and Options
This table shows the part numbering scheme for the full line of SynQor UPS products:
Base Models
Model Number
Power
Battery Run-Time
Height (W x D x H)
Weight
@Full Power (80% Power)
UPS-1500-S-1U (1 Standard Battery Pack)
1250 W 1500 VA
>10 min. (>13 min.)
1U (17.00” x 21.60” x 1.73”)
32 lbs.
UPS-1500-E-2U (1 Extended Battery Pack)
1250 W 1500 VA
>24 min. (>31 min.)
2U (17.00” x 21.60” x 3.33”)
50 lbs.
Base Models
Options
Options
AC
Input
Freq
AC
Output
Voltage
AC
Output
Neutral
Wire
AC
Output
Set
Point
Freq
DC
Input
/ DC2
Output
DC1
Output
Additional
Options
AC Input
Freq
L
W
47-65 Hz
47-800 Hz
AC Output
Voltage
1
2
115 Vrms
230 Vrms
UPS-1500-S-1U-
UPS-1500-E-2U-
L
W
1
2
S
00
-E
00
CE
D
12
G
5
M
15
AC Output
Neutral
Wire
G
F
R
Grounded
F
6
P
24
Floating*
R
4
R
28
AC Output Electronic Breaker*
V
40
AC Output
Set Point
Freq
5
6
4
50 Hz
60 Hz
400 Hz
W
50
Not all combinations make valid part numbers, please contact SynQor for availability.
See the Product Summary web page for more options.
DC Input /
DC2 Output
S Not Installed
*Notes:
D DC Input
Order “F: Floating” option when configuring the AC output for multi-unit combinations
M DC2 Out 24 VDC with Droop Share
of up to 3 units.
P DC2 Out 24 VDC No Share
Order “R: AC Output Electronic Breaker” option for fault-tolerant,
R DC2 Out 28 VDC with Droop Share
glitch-free parallel systems of up to 32 units with N+M redundancy.
V DC2 Out 28 VDC No Share
The AC output neutral wire will not be connected to the chassis.
W DC2 Out 50 VDC No Share
DC1 Output
00 None
12 12 V
Examples:
15 15 V
UPS-1500-E-2U-L1G6D28-E00, UPS-1500-S-1U-L2G5S00-E00
24 24 V
UPS-1500-S-1U-L2G5S00-ECE (230 V output with CE marking)
28 28 V
40 40 V
50 50 V
Additional
Options
-E Ethernet/SNMP with Configuration Loading
00 No CE Marking
CE CE Marking
The UPS-1500 Series of products provide up to 1500 VA and 1250 W of total output power
(AC plus DC). They come in two different physical formats:
• A 1U high, 32 lb. rackmount unit that uses the standard battery pack that provides >10 minutes of battery run-
time at full power
• A 2U high, 50 lb. rackmount unit that uses the extended battery pack that provides >24 minutes of battery
run-time at full power
Each format has various options that can be specified according to the part numbering scheme shown
in the table:
• The allowable frequency of the AC INPUT can either be in the 47-65 Hz range (for 50 Hz and/or 60 Hz systems) or
in the 360-800 Hz range (for 400 Hz and Variable Frequency systems)
• The output voltage of the UPS-1500 Series can be 115 VRMS or 230 VRMS