Section II
General Product Information
006-0007068 UPS-1500-S-2S Guide
Rev E
16 of 60
09/10/20
Furthermore, there is a limited (and uncommon) range of AC INPUT voltage between 132 Vrms
and 160 Vrms in which the total output power that can be derived from the AC INPUT is also
derated, as shown in the graph below.
1100W
0
200
400
600
800
1000
1200
1400
60
80
100
120
140
160
180
200
220
240
260
280
Output
Power
(Watts)
Input Voltage (Vrms)
Output Power vs. AC Input Voltage
(without switching over to the DC input or the battery)
Steady state
15s transient
2s transient
132V
Figure 3
Note that the full rated output power of 1250 W can be derived from the AC INPUT having a voltage
within this uncommon range for 15 seconds before the UPS will switch over to the DC INPUT or the
BATTERY PACK. Also note that the UPS can drive it full rated power for a 2 second interval even if the AC
INPUT voltage drops below 90
Vrms
.