background image

DOC-1000198-B-1

 

 
 

 
 
 
 

 

 

 
PART NUMBER: 

IIOT-REPEATER 

 

DESCRIPTION 

 
The IIOT-REPEATER works in conjunction with other 
Synapse-enabled devices to create a robust mesh network 

for use in a variety of IIoT solutions such as lighting 
controls, energy monitoring and air handling.

 

 

SPECIFICATIONS 

 

 

Voltage Input: 100-277VAC, (+/-10%), 50/60 Hz 

 

Max Current Draw: 3.6W, 30mA at 120VAC or 13mA 
at 277VAC 

 

Radio Frequency: 2.4 GHz (IEEE 802.15.4) 

 

RF Transmission Output Power: +15dBm 

 

Operating Temperature: -40 to +55 C 

 

Operating Humidity: 10 to 90%, non-condensing 

 

Configuration/Programming: Stored in non-volatile 
memory 

 

Enclosure Type: UL94-HB, ABS Plastic 

 

Dimensions: 7.87L x 3.93W X 2.75H in.                    
(200 X 100 X 70 mm) 

 

CAUTION 

 

The IIOT-REPEATER must be installed in accordance 
with national, state, and local electrical codes and 
requirements. 

 

All work must be performed by qualified personnel. 

 

Disconnect all power before installation or service. 

 

 NEEDED MATERIAL 

 

Mounting Hardware:

 Using Hardware appropriate 

for the installation, use all four (4) 0.197” diameter 
mounting holes to mount the unit.  

 

Conduit:

 To maintain the IP rating of the unit, it must 

be installed with the included cable gland

 

OR with a 

weather-proof 

¾

” conduit fitting at the power entry 

point. 

 

 
 
 
 
 
 

 

 

 

INSTALLATION 

1.

 

The IIOT-REPEATER must be mounted vertically with the 

power coming out the bottom of the unit, or the wireless 
signal may be compromised. DO NOT install the IIOT-

REPEATER horizontally.  

 
2.

 

Select an installation location for the IIOT-REPEATER that 
provides line of sight to at least two other Synapse IIOT 
hardware devices. These devices can be another 

repeater, a lighting controller, or the site controller itself. 
It may be necessary to add more than one repeater to 

prevent a single point of failure in the RF network.  
(See Figure 1) 

 

Note:

 

IIOT hardware that utilize sleep mode should not 

be considered part of the IIOT repeater network) 

 

3.

 

The antenna relies on free space around them for best RF 

performance so avoid installation near network cabling, 
AC power lines or within metal enclosures. Finally avoid 

installing the IIOT-REPEATER in direct sunlight.  
 

4.

 

Using Hardware appropriate for the installation, use all 
four (4) 0.197” diameter mounting holes to mount the 

unit. 

 
5.

 

With the IIOT-REPEATER mounted, you must have a 
licensed electrician pull power into the device according 

to national, state, and local electrical codes and 
requirements. The electrician is to connect the LINE and 

NEUTRAL through the power entry point inside the 
device. (See Figure 2) 

 

 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

  

 

 

 

 

 

NOTE:

 A Power entry cable is not provided. The power 

entry point is 

¾

”. The provided cable gland or a sealed 

power entry connector and conduit is required in order to 

maintain the IP65 rating. 

NOTE:

 If multiple conductors pass through the cable 

gland, they must be in a single sheath in order to maintain 

the IP65 rating. Recommended Cable diameter is 4-8 mm. 

NOTE:

 The IIOT-REPEATER holds a IP65 rating when the 

door is latched and all entry points are properly sealed. 

Failure to do so will void the IP65 rating. 

 
 

IIOT-REPEATER 

100-277VAC SimplySNAP Mesh Network Repeater 

Operating Temperature: -40 to +55 C / Operating Humidity: 10 to 90%, non-condensing 

WARNING AND CAUTIONS: 

TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER 

AT CIRCUIT 

BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!

 

Risk of Electric Shock - 

More than one disconnect switch may be required to 

de-energize the equipment before servicing. 

To be installed and/or used in accordance with appropriate electrical codes and 
regulations.

 

 

INSTALLATION GUIDE 

 

WARNING AND CAUTIONS:

 

If you are unsure about any part of these instructions, consult an 
electrician. 

Use this device with copper or copper clad wire only. 

Disconnect power at circuit breaker or fuse when servicing, installing or removing 

fixture or changing lamps. 

Mounting: It is critical to the performance of this device that the antenna be 
oriented vertically. It must point straight up or down for proper operation. 

Figure 2 –Wiring Diagram 