DOC-1000560-B-1
Part Number:
CONTROL-485-101
DESCRIPTION
The Control Thermostat works in conjunction with other
SimplySnap nodes to provide access to BACnet MSTP
thermostats.
SPECIFICATIONS
Input power:
12-24VDC +/-10% or
24VAC +/- 10% from an UL listed Class 2, 24V
transformer (not provided), half-wave compatible.
Dimensions:
7.8” L x 3.9” W x 2.8” H
(200mm x 100mm x 70mm)
IP Rating:
IP-66
Mounting
: Independently surface mounted, Wall or
I-Beam (mounting brackets included)
Control:
Operating (Non-safety) HVAC/MAU control
Supported Thermostats:
Honeywell BACnet FF TB3026
Serial Interface:
RS-485 or RS-422
Baud Rates:
9600, 19200, 38400, 76800 and 115200
Radio:
2.4 GHz (IEEE 802.15.4), +20 dBm Transmit
Power, -103 dBm Receive Sensitivity
Warranty:
1 Year
See www.synapsewireless.com/warranty for warranty
terms.
CAUTION
•
The Control Thermostat hardware must be installed in
accordance with national, state, and local electrical codes
and requirements.
•
All work must be performed by qualified personnel.
• The common signal
from the Control Thermostat
hardware
should not be tied to earth ground.
•
Disconnect all power before installation or service.
INCLUDED MATERIAL
•
2 Cable glands
•
1 Hole plug
•
Mounting brackets
NEEDED MATERIAL
•
Screw Driver
: A #2 Phillips is required to connect the
cables to the terminals.
•
Mounting Screws:
Mounting bracket holes fit #10
screws
•
Conduit:
To maintain the 4X rating of the enclosure, it
must be installed with the 4X ½” cable glands
supplied
or with minimum 4X liquid-
tight ½” conduit fittings, not
supplied, at the power/signal entry points.
INSTALLATION INSTRUCTIONS
1.
Select a suitable installation location for the Control
Thermostat hardware e.g. between the BACnet
thermostat and the HVAC/MAU.
2.
Select between inline or adjacent installation, see
Figure 1 for more details.
3.
Mount the Control Thermostat hardware using the
brackets included.
4.
Open the enclosure cover.
5.
Install
½”
cable gland(s) supplied and torque nuts to
60 in-lbs; or use liquid-tight conduit fittings as
required.
6.
If only one cable entry is used, plug the unused hole
with the liquid-tight plug supplied.
7.
To maintain the IP rating, jacketed cable wires are
recommended with cable
diameter of 0.21” –
0.33”.
Torque sealing cable glands to 40-55 in-lbs,
depending on the cable diameter and jacket
hardness.
8.
AC powered: Connect the AC power wires (e.g. from
the HVAC 24VAC transformer) to wire terminals
COMMON and 24VAC/DC maintaining the correct
polarity. See Figure 2
9.
DC Powered: Connect the DC power supply wire (+)
to 24VAC/VDC and (-) to COMMON.
See Figure 3.
10.
If the Control Thermostat hardware is being
connected inline with the BACnet thermostat,
connect the thermostat power wires to the same
Control Thermostat hardware terminals COM/GND
and 24VAC/DC. See Figure 2
11.
RS-485/BACnet serial connections: Connect the
Control Thermostat screw terminal D+ to MS/TP+ on
the BACnet thermostat, D- to MS/TP- and GND to GND
;or connect to D+ to D+, D- to D- and GND to GND on
any other RS-485 serially controlled devices.
See Figure 4.
12.
Ensure all control lines are reattached to the
thermostat.
13.
Contact Synapse for Support-
(877) 982-7888
Figure 1. Installation options
INSTALLATION GUIDE
WARNINGS AND CAUTIONS:
•
If you are unsure about any part of these instructions, consult an electrician.
•
Use this device with copper or copper clad wire only.
Mounting:
For best RF performance and signal strength, do not mount this device
inside a metal box. Final installed unit should also be mounted with open space on 2 or
more
sides.
Control Thermostat
Operating Temperature: 0C to +60C / Input Power: 12-24VDC or 24VAC, 50-60Hz
WARNINGS AND CAUTIONS:
•
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR
FUSE AND TEST THAT POWER IS OFF BEFORE WIRING!
•
Risk of Electric Shock - More than one disconnect switch may be required to de-
energize the equipment before servicing.
•
To be installed and/or used in accordance with appropriate electrical codes and
regulations.
Inline Installation
Adjacent Installation
Control
Thermostat
Control
Thermostat